Thèse de Doctorat
DOI
https://doi.org/10.11606/T.3.2023.tde-21092023-092123
Document
Auteur
Nom complet
Rodolfo Varraschim Rocha
Adresse Mail
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Paulo, 2023
Directeur
Jury
Monaro, Renato Machado (Président)
Chabu, Ivan Eduardo
Coury, Denis Vinicius
Lima, Francisco Kleber de Araújo
Silva, Kleber Melo e
Titre en portugais
Análise de faltas internas em geradores síncronos de velocidade variável conectados a conversores de três níveis.
Mots-clés en portugais
Faltas entre espiras
Faltas internas
Gerador síncrono
Proteção elétrica
Velocidade variável
Resumé en portugais
Este trabalho traz uma análise detalhada dos efeitos de faltas entre espiras, sem envolvimento com Terra, no enrolamento de estator dos geradores síncronos de polos salientes eletricamente excitados conectados a inversores bidirecionais do tipo Neutral Point Clamped de três níveis. Adicionalmente, é proposto um algoritmo para detecção dessas faltas usando as medidas de correntes elétricas tipicamente adquiridas para fins de controle do gerador para evitar a necessidade de instalação de sensores adicionais. As faltas entre as espiras do estator causam mudanças específicas no conteúdo harmônico das correntes de linha e campo do gerador, as quais são filtradas e usadas para detecção da ocorrência das faltas. A mudança nas características da corrente do neutro do inversor de três níveis conectado ao gerador também é avaliada para detecção das faltas. Para detectar as componentes harmônicas selecionadas em diferentes velocidades, são usados filtros dinâmicos baseados nas transformadas / e de Fourier, que empregam a medida de posição do rotor para se adaptar às mudanças de frequências das componentes sob diferentes velocidades. Então, os lugares geométricos das componentes são propostos como parâmetro para distinguir entre condições saudáveis e defeituosas. Dados de simulação e experimentais são considerados para testar a sensibilidade, seletividade e tempo de detecção da técnica proposta para diferentes casos de faltas. A avaliação para um gerador de 4, 5 MW também é apresentada considerando simulações computacionais.
Titre en anglais
Internal faults analysis in variable speed synchronous generators connected to three-level converters.
Mots-clés en anglais
Internal faults
Protection
Three-level Inverter
Turn faults
Variable-speed
Wound rotor synchronous generator,Salient pole
Resumé en anglais
This work presents a detailed analysis of the effects of turn faults, without ground contact, on the stator winding of electrically excited salient pole synchronous generators connected to three-level Neutral Point Clamped bidirectional inverters. Moreover, an algorithm to detect these faults using measurements of electrical currents typically acquired for control purposes is proposed, in order to avoid the need to install additional sensors. Faults between stator turns cause specific changes in the harmonic content of the generator line and field currents, which are filtered and used for fault detection. The changes in the characteristics of the neutral current of the three-level inverter connected to the generator is also evaluated for fault detection. To detect selected harmonic components at different speeds, dynamic filters based on abc/dq and Fourier transforms are used, which employ the rotor position measurement to adapt to frequency changes of the components under different speeds. Then, the geometric loci are proposed as a parameter to distinguish between healthy and faulty conditions. Simulation and experimental dataare used to test the sensitivity, selectivity and detection time of the proposed technique for different fault cases. The evaluation for a 4.5 MW generator is also performed through computational simulations.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Date de Publication
2023-09-22
 
AVERTISSEMENT: Apprenez ce que sont des œvres dérivées cliquant ici.
Tous droits de la thèse/dissertation appartiennent aux auteurs
CeTI-SC/STI
Bibliothèque Numérique de Thèses et Mémoires de l'USP. Copyright © 2001-2024. Tous droits réservés.