Mémoire de Maîtrise
DOI
https://doi.org/10.11606/D.3.2023.tde-17012024-100630
Document
Auteur
Nom complet
Marcos Frederico Bortotti
Adresse Mail
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Paulo, 2023
Directeur
Jury
Grimoni, Jose Aquiles Baesso (Président)
Barreto, Gustavo de Andrade
Reis Filho, Francisco Antonio
Titre en portugais
Estudo de geração distribuída para redes elétricas subterrâneas do tipo Spot Network -estudo de caso da rede de Brasília.
Mots-clés en portugais
Distribuição de energia elétrica
Eletricidade
Eletrônica
Resumé en portugais
Este estudo de metrado se concentra no desenvolvimento de um protótipo de equipamento destinado à integração na Rede de Distribuição Subterrânea (RDS) da CEB/NDB, visando garantir o funcionamento eficiente da rede em face do aumento da Geração Distribuída (GD). A RDS da CEB/NDB compreende três sistemas de distribuição: o sistema Spot , com transformadores em paralelo e ligações primárias independentes; o sistema Primário Seletivo, com redundância de alimentadores e comutação automática; e o sistema radial , sem redundância. No contexto do sistema Spot Network, o projeto propôs um retrofit nas Estações Transformadoras (ET) para possibilitar sua operação eficaz com a presença da GD. Nas ETs, Protetores d e Rede com relés d e proteção d e potência reversa são utilizados . No entanto, devido às configurações adotadas pela NDB, quantidades mínimas de GD podem desligar a proteção, resultando no isolamento dos consumidores, um fenômeno conhecido como "efeito de ilhamento" e proibido pelo IEEE 1547 e pela ABNT NBR62116. O retrofit inclui a instalação de sensores de corrente nos ramos de baixa tensão da ET e um Concentrador de Geração Distribuída (C-GD) . O CGD monitora o nível de GD na ET e a justa os relés dos Protetores de Rede por meio de algoritmos especializados, permitindo que a potência reversa flua da GD para a rede da NDB. Isso permite a coexistência harmoniosa entre GD e o sistema Spot Network, sem a necessidade de adaptações complexas na rede de distribuição que possam limitar a expansão da GD. Dessa forma, o projeto oferece uma solução prática p ara o desafio persistente da integração da GD, evitando obstáculos que poderiam restringi r a adoção dessas importantes fontes de energia no sistema. O estudo representa um avanço significativo na resolução de um dilema persistente na integração da GD, contribuindo para um sistema de distribuição mais eficiente e sustentável
Titre en anglais
Distributed generation study for underground spot network electrical grids - Brasília network case study.
Mots-clés en anglais
Concentrator of Distributed Generation (C-GD)
Distributed Generation (DG)
Distribution Network
Energy injection
Grid network
IEEE 1547 Standard
Islanding, Harmonious coexistence
Photovoltaic power plants
Redundant network
Research and Development (R&D)
Retrofit
Reverse power protection
Spot network, Network protector
Underground Distribution Network (RDS)
Resumé en anglais
This master's study focuses on the development of a prototype equipmentaimed at integration in to the Underground Distribution Network (UDN) of CEB/NDB, with the goal of ensuring the efficient operation of the network in the face of the increasing Distributed Generation (DG) . CEB/NDB's UDN comprises three distribution systems: the Spot system, with parallel transformers and independent primary connections; the Selective Primary system, with feeder redundancy and automatic switching ; and the radial system, lacking redundancy . In the context of the Spot Network system, the project proposed a retrofit in Transformer Stations (TS) to enable their effective operation in the presence of DG. TSs house Network Protectors with reverse power protection relays. However , due to the configurations adopted by NDB, even small amounts of DG can trip the protection, resulting in the isolat ion of consumers , a phenomenon known as "islanding effect ," and prohibited by IEEE 1547 and by ABNT NBR 62116. The retrofit includes the installat ion of current sensors in the low-voltage output branches of the TS and a Distributed Generation Concentrator (CGD). The C-GD monitors the level of DG in the TS and adjusts the relays of the Network Protectors through specialized algorithms, allowing reverse power to flow from DG to the NDB network . This enables the harmonious coexistence between DG and the Spot Network system without the need for complex adaptations to the distribution network that could limit the expansion of DG. Thus, the project provides a practical solution to the persistent challenge of DG integration, avoiding obstacles that could restrict the adoption of this important energy source in the system.The study represents a significant advancement in addressing a persistent dilemma in DG in tegration, contributing to a more efficient and sustainable distribution system.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Date de Publication
2024-01-18
 
AVERTISSEMENT: Apprenez ce que sont des œvres dérivées cliquant ici.
Tous droits de la thèse/dissertation appartiennent aux auteurs
CeTI-SC/STI
Bibliothèque Numérique de Thèses et Mémoires de l'USP. Copyright © 2001-2024. Tous droits réservés.