Disertación de Maestría
DOI
https://doi.org/10.11606/D.3.2023.tde-04082023-084223
Documento
Autor
Nombre completo
Leonardo do Nascimento Pereira
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2023
Director
Tribunal
Manassero Junior, Giovanni (Presidente)
Lira, George Rossany Soares de
Souza, André Nunes de
Título en portugués
Avaliação da degradação de disjuntores de alta tensão por meio de técnicas de machine learning.
Palabras clave en portugués
Análise de dados
Disjuntores
Manutenção preditiva
Resumen en portugués
O trabalho apresenta uma metodologia para avaliação da degradação de disjuntores de alta tensão ao longo de uma extensa janela temporal. Para isso, foram mapeados disjuntores de uma distribuidora de grande porte. Os disjuntores mapeados tiveram os seus ensaios de resistência de contato, tempo de abertura e tempo de fechamento avaliados. Por se tratar de uma extensa massa de dados, foram utilizadas técnicas de machine learning para clusterização dos disjuntores conforme o seu nível de degradação e, consequentemente, o risco de falha atrelado ao ativo. Foram analisados apenas disjuntores de 138kV isolados a gás SF6. Contudo, os padrões nominais de operação do disjuntor variam de acordo com fabricante e modelo. Neste sentido, fez-se uso de um algoritmo de machine learning (K-Means) para clusterizar as n observações dentre k grupos, onde cada observação pertence ao grupo mais próximo da média. Porém, antes da clusterização, foi aplicada uma técnica de redução de dimensão chamada principal component analysis (PCA). Com isso, é possível obter uma representação em duas dimensões da base de dados - diagrama de Voronoy - dos disjuntores. Finalmente, a análise das propriedades de cada cluster permite identificar equipamentos que apresentam comportamento diferente ao restante de sua família. Esses ativos apresentam um risco maior de falha. Diversos trabalhos foram publicados sobre o uso dos dados de disjuntores para monitoramento da condição, porém, o presente trabalho se diferencia dos demais por utilizar uma base de dados real de ensaios de campo, com grande variação temporal (1977-2021).
Título en inglés
High voltage circuit breaker degradation assessment via machine learning techniques.
Palabras clave en inglés
Circuit-breaker
Data analysis
Predictive maintenance
Resumen en inglés
This dissertation presents a methodology for evaluation of high voltage circuit breaker s degradation over a large time window. For this, circuit breakers of a large distribution company were mapped. The mapped circuit breakers had their contact resistance tests, opening time and closing time evaluated. Because it is a large mass of data, machine learning techniques were used to cluster the circuit breakers according to their level of degradation and, consequently, the operational risk linked to the asset. Only SF6 gas insulated circuit breakers with rated operational voltage of 138kV were analyzed. However, the rated operating standards of the circuit breaker vary by manufacturer and model. In this sense, a machine learning algorithm (K-Means) was used to cluster n samples among k groups, where each sample belongs to the closest group. However, before clustering, a dimension reduction technic was applied (principal component analysis - PCA). Then, it is possible to obtain a two dimension representation of the original database which enables the creation of Voronoys diagrams of the clusters. So, it is possible to identify equipment that behaves differently from the rest of their family. These assets have a higher risk of failure. Several works have been published on the use of circuit breaker data to monitor assets condition, however, the present work differs from the others because it uses a real database of field testes, with wide temporal variation (1977-2021).
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2023-08-04
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.