Tesis Doctoral
DOI
https://doi.org/10.11606/T.3.2000.tde-24012024-142901
Documento
Autor
Nombre completo
Antonio Luis de Campos Mariani
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2000
Director
Tribunal
Pimenta, Marcos de Mattos (Presidente)
Peixoto, Roberto de Aguiar
Pereira, Marcos Tadeu
Roma, Woodrow Nelson Lopes
Yanagihara, Jurandir Itizo
Título en portugués
Estudo experimental de escoamentos turbulentos em passagens curtas com sensores multífuros multidirecionais.
Palabras clave en portugués
Ar condicionado
Escoamento
Vetores
Resumen en portugués
Este trabalho teve como proposta investigar a interação entre o escoamento de ar em uma passagem curta, que representa uma tomada de ar externo de um sistema de ar condicionado, e uma grade sensora multidirecional desenvolvida para avaliar vetores de velocidades médias na seção onde deseja-se medir a vazão. Nesta passagem curta foi estabelecida uma seção de medição localizada entre a veneziana e o registro e filtro. Para determinar o campo de velocidades na passagem curta com a presença de acessórios foram realizadas medições com sistema de anemometria laser. O intervalo de vazões foi de 0.200'm POT. 3'/s a 0.640'm POT. 3'/s, determinado a partir dos acessórios selecionados para a simulação. Um conceito novo de sondas cilíndricas multifuradas multidirecionais foi desenvolvida a partir dos resultados obtidos para os perfis de velocidade. Para capacitar as sondas cilíndricas para medir velocidade e direção do escoamento foram realizados simulações numéricas e ensaios experimentais com número de Reynolds no intervalo 2000 < Red < 10000. Os parâmetros de direcionalidade foram obtidos a partir dos resultados da distribuição de pressões no cilindro sensor. Modelo semi-empírico definiu números adimensionais, cujas curvas viabilizaram a aplicação dos sensores. Para os ensaios que simularam a aplicação de um protótipo da grade sensora em uma tomada de ar externo, foi projetado e fabricado, um módulo experimental com a simulação de uma câmara de mistura de uma instalação de ar condicionado, um sistema monitor de pressões multicanal acoplado a um microcomputador que fez o gerenciamento e tratamento dos dados, e uma grade sensora multifurada multidirecional. Os resultados dos ensaios no módulo experimental apresentaram valores de velocidade e vazão na seção de medição próximos àqueles medidos com o anemômetro laser e placa de orifício, adotada como padrão de referência de vazão. Estes resultados indicaram que para a ) metodologia de cálculo de vazão adotada ocorreu uma diferença da ordem de 2,8% para configuração com veneziana, 1,5% para configuração com veneziana e filtro e 3,2% para a configuração com os três acessórios. As curvas que relacionam vazão medida com a grade e com a placa tiveram comportamento linear, indicando a possibilidade de seu uso em sistemas de controle.
Título en inglés
Untitle in english
Palabras clave en inglés
Air conditioning
Drainage
Vectors
Resumen en inglés
The main objective of this study is the investigation o fair flow in short passages o fair conditioning mixing chamber inlets, and its interaction with a multidirectional sensor grid, developed to measure average velocities in a cross section. In this short passage it is defined a measuring cross section between the louvers and the damper and filter. In order to determine the velocities in this short passage with the effect of accessories, measurements are performed with laser anemometry. The interval of flowrates, 200 m³/s a 0.640 m³/s, was determined from the selection of accessories for this simulation. A new concept of multidirectional and multiholed cylindrical probe was develop from the analysis of the velocity profiles. To making possible these cylindrical sensors to measure flow velocity and direction, on performed numerical simulations and experimental tests as Reynolds numbers 2000 < Red < 10000. The directionality parameters were obtained from the pressure distribution around the cylindrical sensor. A semi empirical model was defined non-dimensional numbers, giving curves and correlations that made possible the sensor application. This tests to simulate the application of the grid prototype for on external air intake were developed and built on experimental test apparatus simulating on air conditioning mixing chamber, a pressure monitoring system attached to a microcomputer which menages and treats the data from the sensing grid. The test results from the experimental apparatus presented velocity and flowrate values close to those measured with laser anemometry and orifice plate adopted as reference. These results, indicated for the adopted evaluation show a difference of 2.8% with the louver configuration, 1.5% for louver plus filter and 3.2% in the with on three accessories. The flow curves with the grid and plate present a linear behavior, which indicates the possibility of its use in control systems.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2024-01-24
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.