Disertación de Maestría
DOI
https://doi.org/10.11606/D.6.2009.tde-20072009-154521
Documento
Autor
Nombre completo
Helder Yudji Etto
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2009
Director
Tribunal
Razzolini, Maria Tereza Pepe (Presidente)
Hachich, Elayse Maria
Matte, Glavur Rogerio
Título en portugués
Detecção de bactérias do gênero Legionella em amostras de água provenientes de sistemas de ar condicionado
Palabras clave en portugués
Água
Legionella
Sistemas de Ar Condicionado
Resumen en portugués
Introdução: Destaca-se a importância dos organismos do gênero Legionella como agentes causadores de doenças do aparelho respiratório como a legionelose ou doença do Legionário, e ainda de um controle na manutenção adequada de sistemas de ar condicionado, uma vez que estes foram identificados como ambientes favoráveis à proliferação desses microrganismos. Objetivo: Devido à importância de bactérias do gênero Legionella como agentes causadores de doenças, e um crescente número de casos de legionelose relacionados à permanência em ambientes fechados, este estudo teve como objetivo determinar a presença de Legionella em águas de bandejas de sistemas de ar condicionado. Métodos: Foram realizadas análises de amostras de água provenientes de bandejas de ar condicionado de dois hospitais, uma instituição de ensino superior e um centro comercial, totalizando 41 amostras. Volumes de 1L das amostras coletadas foram concentrados em membrana, seguida de tratamento ácido. Alíquotas das amostras tratadas e não tratadas com ácido, foram então inoculadas em meio Agar BCYE-, com e sem adição de antibióticos. As cepas isoladas foram submetidas a teste sorológico para identificação. Resultados: Das amostras analisadas, 4 (9,5%) apresentaram resultado positivo para Legionella sp.; uma no centro comercial e três em um dos hospitais estudados. Os isolados foram submetidos a teste sorológico, sendo um identificado como Legionella pneumophila sorogrupo 1 e três como seis prováveis espécies:L. longbeachae, L. bozemanni, L. dumoffi, L. gormanii, L. jordanis, L. micdadei, L. anisa . Conclusão: Os resultados deste estudo comprovam a presença de Legionella sp. nos sistemas de ar condicionado pesquisados, sendo observada maior freqüência dos isolados em amostras analisadas oriundas dos hospitais.Os resultados demonstraram a importância e a necessidade de planos de monitoramento em sistemas de 7 ar condicionado como medida preventiva à colonização por organismos patogênicos nesses sistemas e dessa forma proteger a saúde dos ocupantes e usuários de ambientes climatizados artificialmente.
Título en inglés
Detection of bacteria genus Legionella in water samples of airconditioning systems [master degree]
Palabras clave en inglés
Air-Conditioning Systems
Legionella
Water
Resumen en inglés
Introduction: It highlights the importance of organisms genus Legionella as responsible for diseases of the respiratory system such as legionellosis or Legionnaires´disease, and a control on proper maintenance of air conditioning systems, as these were identified as favorable environment for the proliferation of these microorganisms. Objective: Due to the importance of Legionella as causative agents of disease and a growing number of cases of legionellosis related to stay indoors, this study aimed to determine the presence of Legionella in water samples from air-conditioning systems. Methods: We performed analysis of samples of water from trays of airconditioning systems in two hospitals, a university and a trade center, totalizing 41 samples. One liter volumes of water samples were concentrated on membrane, followed by acid treatment. Aliquots of the sample treated and not treated with acid, were inoculated on BCYE- agar medium, with and without added antibiotics. The strains were subjected to serological identification. Results: Out of the samples analyzed, 4 (9.5%) were positive for Legionella sp.; one in a trade center and three in one of the hospitals. Isolates were submitted to serological testing, one identified as Legionella pneumophila serogroup 1 and three as probable six species: L. longbeachae, L. bozemanni, L. dumoffi, L. gormanii, L. jordan, L. micdadei, L. anise. Conclusion: The results confirm the presence of Legionella sp. in air conditioning systems studied. It was observed a higher frequency in isolates from hospitals. The results demonstrated the importance and necessity of monitoring plans in air-conditioning systems as a preventive measure to colonization by pathogens in these systems and protect the health of occupants and users of these buildings.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
HelderEtto.pdf (1.34 Mbytes)
Fecha de Publicación
2009-08-04
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.