Master's Dissertation
DOI
https://doi.org/10.11606/D.3.2023.tde-31072023-151149
Document
Author
Full name
João Cardoso das Neves Neto
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2023
Supervisor
Committee
Almeida, Carlos Frederico Meschini (President)
Arruda, Elcio Franklin de
Rosa, Luiz Henrique Leite
Title in Portuguese
Investigação da frequência de ressonância com compensação reativa através da análise da qualidade da energia elétrica em instalações elétricas hospitalares com equipamentos.
Keywords in Portuguese
Compensação reativa
Frequência de ressonância
Instalações elétricas (Qualidade)
Instalações hospitalares
Ressonância harmônica
Abstract in Portuguese
Com o advento da pandemia da covid-19 e com o avanço da tecnologia dos equipamentos eletromédicos, as atenções à saúde, de modo geral, e a preocupação com a Qualidade da Energia Elétrica nas instalações elétricas hospitalares e clínicas de diagnósticos por imagem ganharam maior atenção, buscando um perfeito desempenho de seus equipamentos, pois uma má Qualidade da Energia Elétrica pode impactar nos diagnósticos médicos através do surgimento de interferências nas imagens, prejudicando a interpretação médica. Foram desenvolvidas normativas eficazes que indicam os requisitos técnicos necessários para garantir a conformidade dessas instalações, porém não há estudos completos sobre a imunidade e a emissividade dos equipamentos eletromédicos quanto a Qualidade da Energia. Esta pesquisa investiga a frequência de ressonância harmônica com a compensação de energia reativa através de bancos de capacitores aplicados no circuito elétrico, que consiste em um equipamento de Ressonância Magnética de Imagem (MRI), bem como procura auxiliar na determinação da melhor metodologia para a mitigação das correntes harmônicas. Com o intuito de buscar a determinação de um método para o dimensionamento das instalações médicas, também foi realizado um estudo paramétrico sobre a frequência de ressonância a partir da variação da potência reativa instalada e a impedância percentual do transformador alimentador do sistema e a determinação de um valor percentual (p%) para o melhor dimensionamento do filtro antirressonante. Para um melhor entendimento da metodologia, foram aplicados os conceitos de compensação reativa e aplicado os conceitos da IEC60831-1, corrente de trabalho circulante em capacitores acima considerando 30% da nominal e a atenuação dos harmônicos do sistema com implementação de filtros antirressonantes ou não. Assim, após a compensação do fator de potência, houve a necessidade de dimensionamento do filtro devido ao surgimento das ressonâncias harmônicas. Contudo, para um correto dimensionamento das compensações, a preocupação com os harmônicos e suas consequências são de suma importância.
Title in English
Resonance frequency investigation with reactive compensation through power quality analysis in hospital electrical installations with radiological equipment.
Keywords in English
Anti-resonant filter
Harmonic distortions
Harmonic resonance MRI
Power quality
Abstract in English
With the advent of the covid-19 pandemic and the advancement in technology of electromedical equipment, attention to health, in general, and the concern with the Power Quality in hospital electrical installations and imaging diagnosis clinics have gained greater attention, seeking a perfect performance of their equipment, because a poor Power Quality can impact on medical diagnoses through the appearance of interferences in the images, impairing the medical interpretation. Effective norms have been developed that indicate the technical requirements necessary to ensure the compliance of these installations, but there are no complete studies on the immunity and emissivity of electromedical equipment regarding Power Quality. This research investigates the harmonic resonance frequency with reactive power compensation through capacitor banks applied in the electrical circuit, which consists of a Magnetic Resonance Imaging (MRI) equipment, as well as seeks to assist in determining the best methodology for the mitigation of harmonic currents. To seek the determination of a method for the sizing of medical facilities, a parametric study on the resonance frequency from the variation of the installed reactive power and the percentage impedance of the transformer feeding the system and the determination of a percentage value (p%) for the best sizing of the anti-resonant filter was also carried out. For a better understanding of the methodology, the concepts of reactive compensation were applied, and the IEC60831-1 concepts were applied, circulating working current in capacitors above considering 30% of the nominal and the attenuation of the system harmonics with the implementation of anti-resonant filters or not. Thus, after the power factor compensation, there was the need for filter sizing due to the appearance of harmonic resonances. However, for a correct sizing of the compensations, the concern with harmonics and its consequences are of utmost importance.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2023-08-01
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.