Disertación de Maestría
DOI
https://doi.org/10.11606/D.3.2016.tde-20072016-092205
Documento
Autor
Nombre completo
Ricardo Souza Figueredo
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2015
Director
Tribunal
Matakas Junior, Lourenço (Presidente)
Cavalcanti, Marcelo Cabral
Villalva, Marcelo Gradella
Título en portugués
Corrente de fuga em inversores monofásicos sem transformador para conexão de sistemas fotovoltaicos à rede de distribuição de energia elétrica: análise e proposta de filtro passivo integrado de modo comum e diferencial.
Palabras clave en portugués
Amortecimento passivo
Corrente de fuga
Eletrônica de potência
Energia solar
Filtro de modo comum
Filtro de modo diferencial
Filtro LCL
Inversor sem transformador
Sistema fotovoltaico conectado à rede
Resumen en portugués
Este trabalho apresenta um estudo sobre a corrente de fuga de modo comum em inversores monofásicos sem transformador utilizados para a conexão de sistemas fotovoltaicos (FV) à rede de distribuição de energia elétrica. O estudo se concentra em inversores do tipo fonte de tensão que empregam a topologia em ponte completa. A partir da adequada modelagem do sistema (rede, conversor e módulo fotovoltaico) identifica-se e quantifica-se a contribuição das tensões de modo comum e modo diferencial para a corrente de fuga. Conclui-se que a tensão de modo comum de alta frequência produzida pelo inversor, que depende da estratégia de modulação por largura de pulso (PWM Pulse Width Modulation) empregada, fornece a maior contribuição para produção da corrente de fuga. Esse estudo mostra que os inversores sem transformador, com topologia em ponte completa e modulação que produz tensão de saída com três níveis, necessitam de medidas adicionais para a minimização da corrente fuga quando aplicados em sistemas fotovoltaicos conectados à rede. Algumas soluções propostas na literatura para a minimização da corrente de fuga baseadas em topologias modificadas e filtros de modo comum são listadas e discutidas. Neste trabalho é proposto um filtro integrado de modo comum e modo diferencial com amortecimento passivo de baixas perdas, para minimizar a corrente de fuga produzida por um inversor monofásico sem transformador. Um exemplo de aplicação do filtro proposto é apresentado juntamente com seu procedimento de projeto, resultados de simulação e experimentais que validam a proposta. Além disso, a influência da variação da indutância da rede elétrica e da capacitância parasita do sistema fotovoltaico no comportamento do filtro proposto é analisada. A influência da variação da indutância da rede no comportamento do sistema de controle e o impacto da corrente de modo comum no projeto dos indutores do lado do conversor também são analisados.
Título en inglés
Leakage current in single-phase transformerless inverters for the connection of photovoltaic systems to the distribution grid: analysis and proposal of an integrates common and differential mode passive filter.
Palabras clave en inglés
Common mode filter
Differential mode filter
Grid-connected photovoltaic system
LCL filter
Leakage current
Passive damping
Power electronics
Transformerless inverter
Resumen en inglés
This paper presents a study on the common mode leakage current in single-phase transformerless inverters for grid-connected photovoltaic (PV) systems. The study focuses on voltage source inverters (VSI) employing the full-bridge topology. The common mode and differential mode voltages that contribute to the leakage current are identified and quantified from the analysis of the system model (utility grid, converter and PV module). The system model analysis shows that the high frequency common mode voltage produced by the inverter, which depends on the Pulse Width Modulation (PWM) strategy, is the main source contributing to the leakage current. This work shows that transformerless inverters employing the full-bridge topology and a modulation strategy that produces a three-level output voltage require some leakage current minimization strategy when they are employed in grid-connected PV systems. Some solutions proposed in the literature for leakage current minimization based on modified topologies and common mode filters are listed and discussed. In this dissertation an integrated common and differential filter with low loss passive damping is proposed to minimize the leakage current produced by a single-phase transformerless PV inverter. An application example of the proposed filter is presented with design procedure, simulation and experimental results validating the proposal. Additionally, the influence of grid inductance and PV module parasitic capacitance variations on the behavior of the proposed filter is analyzed. The behavior of the control system considering the grid inductance variation and the impact of the common mode current on the converter side inductors design are also analyzed.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2016-07-20
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.