Título en portugués
Estudo de controle e proteção de geradores duplamente alimentados em sistemas eólicos.
Palabras clave en portugués
Conversor back-to-back
Energia eólica
Gerador DFIG
Gerador eólico
Resumen en portugués
O aumento da demanda energética mundial e a necessidade de obtenção de energia por fontes renováveis abriram espaço para discussão sobre vantagens e desvantagens relacionadas às diversas tecnologias de geração existentes. Dados mostram um crescimento significativo do percentual da geração eólica no sistema energético mundial tornando factível o investimento em tecnologias que possam atender às diferenças de aplicação para cada região. Este trabalho apresenta inicialmente as principais características das arquiteturas construtivas dos geradores eólicos listando e apresentando seus principais equipamentos e funções, em seguida são apresentados métodos de controle e proteção aerodinâmica e as principais topologias aplicadas na geração eólica de energia. A discussão das vantagens e desvantagens de cada topologia apontou o gerador Doubly Fed Induction Generator (DFIG) aplicado em sistemas de velocidade variável como uma tecnologia que se destaca pelo seu alto nível de controle e pelo ganho relacionado ao conversor back-to-back de apenas 30% da capacidade de geração da máquina. No trabalho o controle do conversor back-to-back foi testado e validado por simulações e os ajustes dos controladores obtidos pelo método do modelo simétrico ótimo. Em seguida, são apresentados os dispositivos básicos de proteção correlacionados ao monitoramento de corrente, tensão e fluxo de potência e discutidas suas limitações na topologia com o gerador DFIG. No final do trabalho a proteção diferencial é apresentada e aplicada sobre o gerador DFIG e simulações de falta são realizadas em diferentes condições de funcionamento da máquina de modo a obter dados que possam apontar a melhor parametrização deste dispositivo de proteção.
Título en inglés
Study of control and protection of doubly fed induction generator in wind systems.
Palabras clave en inglés
Back-to-back converter
DFIG generator
Faults
Protection
Wind energy
Wind generator
Resumen en inglés
The world energetic demand increase and the generation renewable necessity allowed the dialogue about the advantages and disadvantages of generations technologies existing. Many data shows an significant increase of wind generation inside the world energetic system allowing the investment in technologies to work at the characteristics existing in each place. This study shows the main constructive characteristics in the wind generation showing their main equipments and functions. After, the control and protection aerodynamic methods are shown together with the main topologies in the wind generation. The discussion about the advantages and disadvantages of this topologies showed the DFIG generator working in variable speeds systems like an efficient technology because your accurate control and the low cost of back-to-back frequency inverter. In this study the control of back-to-back converter was tested end validated and the drivers parameters was calculated with the method of the optimal symmetric model. then, are showed some basic protections devices linked with current, voltage and power flow monitoring and yours limitations are discussed in the DFIG topology. In the end the differential protection is showed and applied in the DFIG machine then fault simulations are make to obtain data to produce the best configuration parameters of differential protection.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2017-11-08
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.