Estudo teórico-experimental de método de cálculo para a determinação de cargas térmicas, da temperatura e da umidade do ar de ambientes condicionados.
Keywords in Portuguese
Ar condicionado
Edificações
Abstract in Portuguese
O uso de softwares de simulação têm-se tornado prática cada vez mais frequente nas atividades de avaliação de desempenho térmico de edificações e projeto de sistemas de ar-condicionado. Entre estes softwares, destaca-se o programa NBSLD, pelo detalhamento do modelo matemático empregado na simulação das trocas térmicas que ocorrem em um ambiente. Visando validar suas principais hipóteses simplificadoras e implementar seu código fonte, a fim de contornar algumas limitações existentes, foram realizadas análises numéricas para alguns projetos típicos de edificação e medições em um recinto, estando este condicionado e não-condicionado. Avaliou-se o efeito da linearização das equações de troca de calor por radiação, da fixação dos coeficientes de convecção na face interna das paredes e do emprego das temperaturas do dia anterior ao analisado na exatidão do cálculo. Foram elaborados rotinas e algoritmos que permitissem avaliar a convergencia do processo de cálculo, estimação da variação das propriedades óptico-solares dos vidros em função do ângulo de incidencia da radiacao solar, determinar a umidade do ar quando o recinto não está condicionado e estimar os coeficientes de troca de calor por convecção natural na face interior das vedações. Este último elemento se mostrou de importância fundamental para a exatidão do cálculo.
Title in English
Untitled in english
Keywords in English
Air conditioning
Buildings
Abstract in English
Simulation software is a common tool in building termal evaluation anda ir conditioning systems designs activities. The NBSLD program is one of the most importante by its detailed mathematical modelo f heat changes inside a environment. To validate its main hipotesis and improve its source code, was made numerical analisys considering some typical buildings designs and measurements in a test room. Was evaluated the effect of linearization of radiante heat changes, the natural convective coeficiente inside the room and previous temperature values in the accuracy of calculation. Also, was developed routines to check the calculation convergence, to calculate solar-optical properties of fenestration, to determinate the relative humidity inside unconditioned rooms and evaluate the natural convective heat change coeficiente inside the room. The last one was found be critical to the accuracy of calculation.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2024-04-08
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.