• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Tesis Doctoral
DOI
https://doi.org/10.11606/T.18.2022.tde-27052022-081651
Documento
Autor
Nombre completo
Robson Almir de Oliveira
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2022
Director
Tribunal
Júnior, José Carlos de Melo Vieira (Presidente)
Alberto, Luís Fernando Costa
Lopes, Felipe Vigolvino
Neves, Washington Luiz Araújo
Tavares, Maria Cristina Dias
Título en portugués
Proteção contra perda de sincronismo de geradores síncronos baseada na derivada da potência elétrica
Palabras clave en portugués
Estabilidade de SEP
Geração de energia elétrica
Proteção contra perda de sincronismo
Simulação digital em tempo real
Resumen en portugués
O sistema elétrico de potência deve ser capaz de operar mesmo quando sujeito a eventos de grandes impactos. A resposta a estes eventos envolve uma grande excursão do ângulo do rotor dos geradores, que pode resultar em separação do sistema, em que as ilhas formadas podem ou não se manter em sincronismo. A proteção contra perda de sincronismo (PPS) vem para prover a adequada separação do sistema bem como para proteger os equipamentos da operação fora de sincronismo. Em geradores, a PPS visa evitar severos problemas mecânicos e térmicos, e se baseia na medição da impedância durante o evento, em que a resistência medida (equivalente à potência ativa) tem seu sinal invertido. No entanto, foram identificados casos reais de falha da PPS em que ocorre a perda do sincronismo e a resistência medida não inverte o sinal. Isso ocorre quando há cargas com controle de potência constante próximas a geradores, como no sistema de corrente contínua que interliga a usina de Itaipu 50 Hz ao sistema elétrico brasileiro e demais conexões com os sistemas elétricos paraguaio e argentino. Neste sentido, este trabalho propõe uma nova metodologia baseada na derivada da potência elétrica para identificar perda de sincronismo quando o gerador apresenta parte da potência constante bem como para casos em que a perda de estabilidade leva à queda da frequência do gerador. Os resultados revelaram a capacidade do método em detectar a perda de sincronismo em diversas condições de defeito e a sua segurança em não atuar em situações de oscilações estáveis. Além disso, a proteção desenvolvida foi implementada em um relé comercial e validada por meio de simulações em tempo real, utilizando um Real Time Digital Simulator.
Título en inglés
Synchronous generator out-of-step protection based on electrical power derivative
Palabras clave en inglés
Electric power generation
Out of step protection
Power system stability
Real Time Digital Simulation
Resumen en inglés
The electrical power system must operate even when subjected to events of significant impact. The response to these events involves a large excursion of the generator rotor angle, which can result in system separation, forming islands that may remain or not in synchronism. Out-of-step protection (OOSP) comes to provide adequate system separation and protect equipment against out-of-step operation. OOSP aims to avoid severe mechanical and thermal problems in generators and is based on the impedance measurement during the event. Usually, during an OOS condition, the measured resistance (equivalent to active power) inverts its signal. However, real cases of OOSP failure in which synchronism is lost have been identified, and the measured resistance does not invert the signal. This occurs when loads with a constant power control operate close to generators, as in the High-Voltage Direct Current system that interconnects the Itaipu 50 Hz plant to the Brazilian electrical system and other connections with the Paraguayan and Argentine electrical system. In this sense, this work proposes a new methodology based on the electrical power derivative to identify loss of synchronism when the generator presents part of the constant generated power and for cases in which the loss of stability leads to a drop in the generator frequency. The results revealed the method's ability to detect the loss of synchronism in different fault conditions and its safety in not acting in situations of stable oscillations. In addition, the protection developed was implemented in a commercial relay and validated through real-time simulations using a Real-Time Digital Simulator.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.