Master's Dissertation
DOI
https://doi.org/10.11606/D.18.2012.tde-25042012-154748
Document
Author
Full name
Thais Reggina Kempner
Institute/School/College
Knowledge Area
Date of Defense
Published
São Carlos, 2012
Supervisor
Committee
Oleskovicz, Mário (President)
Arruda, Elcio Franklin de
Vieira Júnior, José Carlos de Melo
Title in Portuguese
A robustez de um sistema de distribuição e a alocação de medidores de qualidade da energia elétrica frente aos afundamentos de tensão
Keywords in Portuguese
Afundamentos de tensão
Alocação ótima de medidores de qualidade da energia
Método das posições de falta
Qualidade da energia elétrica
Sistemas de distribuição
Abstract in Portuguese
Esta dissertação tem como objetivo inicial reapresentar e difundir o Método das Posições de Falta (MPF) como um meio analítico para se determinar as tensões remanescentes, em todas as barras constituintes de um Sistema de Distribuição (SD), quando da ocorrência de afundamentos de tensão. Pela aplicação de tal método, é possível construir a Matriz de Tensão Durante a Falta (MTDF), denotando assim, a influência e a propagação dos afundamentos de tensão sobre toda a rede. A fim de validar o MPF, será realizada uma comparação dos resultados obtidos com os provenientes de simulações computacionais dispondo do software ATP (Alternative Transients Program). Desta comparação, ilustra-se que a ferramenta indicada mantém a previsão dos resultados em limites aceitáveis, mesmo considerando certa simplificação nos procedimentos de cálculo e na modelagem computacional dos componentes do sistema. A partir dos resultados encontrados, é realizado um mapeamento das áreas de risco que equipamentos eletroeletrônicos sensíveis estarão submetidos, através da delimitação e análise da área afetada e da área exposta ou de vulnerabilidade. Em complementação ao trabalho, é apresentada uma proposta baseada em um algoritmo branch and bound que determinará o número ótimo de medidores de qualidade de energia, bem como as barras onde os mesmos devam ser instalados para monitorar os afundamentos de tensão, com o objetivo de garantir que ao menos um dos medidores seja sensibilizado para cada um dos curtos-circuitos simulados.
Title in English
The robustness of a distribution system and an allocation of power quality monitors in the face of the voltage sags
Keywords in English
Distribution systems
Fault position method
Optimal allocation of power quality monitors
Power quality
Voltage sags
Abstract in English
This dissertation aims to initially reintroduce and spread the Fault Positions Method (FPM) as an analytic means to determine the remaining voltage in all bus bar constituents of a Distribution System (DS), upon the occurrence of voltage sags. By applying this method, it is possible to formulate the during fault voltage matrix, thus denoting the influence and propagation of voltage sags around the network as a whole. In order to legitimate the FPM, the results obtained are compared to those from computer simulations by use of the ATP (Alternative Transients Program) software. This comparison demonstrates that the tool has maintained the predicted results within acceptable limits, even though some simplification in the procedure for calculating and computer modeling of the system components. Based on such results, a detailed mapping of areas of risk, to which sensitive electronic equipment is subjected, has been carried out through the outlining and analyzing of the affected area and of the exposed or vulnerability area. Adding up to the work, a proposal based on a branch and bound algorithm is presented as a means to determine the optimum number of power quality monitors, and the bus where they should be installed to measure voltage sags, in order to ensure that at least one of the meters is sensitized for each of the simulated short-circuits.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.