• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Mémoire de Maîtrise
DOI
https://doi.org/10.11606/D.18.2012.tde-16042012-155039
Document
Auteur
Nom complet
Rogério Cesar Serapião Silva
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Carlos, 2012
Directeur
Jury
Coury, Denis Vinicius (Président)
Oleskovicz, Mério
Santos, Ricardo Caneloi dos
Titre en portugais
Projeto diferencial de geradores síncronos: o uso de redes neurais artificiais para identificação e correção da saturação dos transformadores de corrente
Mots-clés en portugais
Geradores síncronos
Proteção diferencial
Redes neurais artificiais
Saturação dos transformadores de corrente
Resumé en portugais
Este trabalho tem como objetivo apresentar um algoritmo de proteção diferencial de geradores baseado em Redes Neurais Artificiais (RNAs), que seja robusto e confiável em situações onde os algoritmos padrões podem apresentar dificuldades, como no caso, da saturação de TCs. O algoritmo desenvolvido é constituído por dois módulos principais: a) um módulo de detecção da saturação dos transformadores de corrente (TCs) empregados na proteção diferencial de geradores e; b) um módulo de correção das formas de onda distorcidas devido à saturação dos TCs. Os módulos utilizam RNAs para detectar e corrigir situações onde haja saturação dos TCs, a fim de evitar a má operação da proteção diferencial. O algoritmo foi desenvolvido em ambiente Matlab e validado com base nos dados da modelagem e simulações de um sistema elétrico utilizando o software Alternative Transients Program (ATP).
Titre en anglais
Differential protection for synchronous generators: the use of artificial neural networks for identification and correction of the saturation of current transformers.
Mots-clés en anglais
Differential protection. Artificial neural networks. Power generator. Current transformer saturatio
Resumé en anglais
This work has as objective to present an algorithm for differential protection of generators based on Artificial Neural Networks (ANN), which is robust and reliable in situations where standard algorithms fail, as in the case of Current Transformer (CT) saturation. The algorithm developed consists of two main modules: a) a module to detect saturation of CTs used in differential protection of generators and; b) module to correct distorted waveforms due to CT saturation. The modules use ANNs to detect and correct situations where there is saturation of CTs in order to avoid misoperation of the differential protection. The algorithm was developed using Matlab software and validated based on data modeling and simulations of a power system using the Alternative Transients Program (ATP) software.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.