Disertación de Maestría
DOI
https://doi.org/10.11606/D.18.2012.tde-16042012-155039
Documento
Autor
Nombre completo
Rogério Cesar Serapião Silva
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2012
Director
Tribunal
Coury, Denis Vinicius (Presidente)
Oleskovicz, Mério
Santos, Ricardo Caneloi dos
Título en portugués
Projeto diferencial de geradores síncronos: o uso de redes neurais artificiais para identificação e correção da saturação dos transformadores de corrente
Palabras clave en portugués
Geradores síncronos
Proteção diferencial
Redes neurais artificiais
Saturação dos transformadores de corrente
Resumen en portugués
Este trabalho tem como objetivo apresentar um algoritmo de proteção diferencial de geradores baseado em Redes Neurais Artificiais (RNAs), que seja robusto e confiável em situações onde os algoritmos padrões podem apresentar dificuldades, como no caso, da saturação de TCs. O algoritmo desenvolvido é constituído por dois módulos principais: a) um módulo de detecção da saturação dos transformadores de corrente (TCs) empregados na proteção diferencial de geradores e; b) um módulo de correção das formas de onda distorcidas devido à saturação dos TCs. Os módulos utilizam RNAs para detectar e corrigir situações onde haja saturação dos TCs, a fim de evitar a má operação da proteção diferencial. O algoritmo foi desenvolvido em ambiente Matlab e validado com base nos dados da modelagem e simulações de um sistema elétrico utilizando o software Alternative Transients Program (ATP).
Título en inglés
Differential protection for synchronous generators: the use of artificial neural networks for identification and correction of the saturation of current transformers.
Palabras clave en inglés
Differential protection. Artificial neural networks. Power generator. Current transformer saturatio
Resumen en inglés
This work has as objective to present an algorithm for differential protection of generators based on Artificial Neural Networks (ANN), which is robust and reliable in situations where standard algorithms fail, as in the case of Current Transformer (CT) saturation. The algorithm developed consists of two main modules: a) a module to detect saturation of CTs used in differential protection of generators and; b) module to correct distorted waveforms due to CT saturation. The modules use ANNs to detect and correct situations where there is saturation of CTs in order to avoid misoperation of the differential protection. The algorithm was developed using Matlab software and validated based on data modeling and simulations of a power system using the Alternative Transients Program (ATP) software.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Rogerio.pdf (2.72 Mbytes)
Fecha de Publicación
2012-04-20
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.