Disertación de Maestría
DOI
https://doi.org/10.11606/D.18.2013.tde-10102013-145542
Documento
Autor
Nombre completo
Rogerio Lucio Lima
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2013
Director
Tribunal
Vieira Júnior, José Carlos de Melo (Presidente)
Ramos, Rodrigo Andrade
Santos, Ricardo Caneloi dos
Título en portugués
Análise de requisitos técnicos para ilhamento intencional de geradores síncronos distribuídos
Palabras clave en portugués
Geração distribuída
Gerador síncrono
Ilhamento
Qualidade da energia elétrica
Rejeição de carga
Resumen en portugués
Havendo qualquer distúrbio em um determinado sistema de distribuição de energia elétrica na presença de geradores distribuídos (GDs), é procedimento habitual exigido pelas concessionárias a desconexão destes na intenção de evitar a formação de um sistema ilhado eletricamente sustentado. Este procedimento tem como objetivo evitar maiores danos tanto ao sistema elétrico como um todo, principalmente ao próprio gerador distribuído, bem como às pessoas envolvidas na manutenção desse sistema. Entretanto, esse fato diminui consideravelmente as contribuições do conceito de geração distribuída à melhoria da qualidade dos serviços de fornecimento de energia elétrica por parte das concessionárias. Neste contexto, este trabalho possui como objetivo analisar os requisitos técnicos necessários para viabilizar a operação ilhada dos geradores distribuídos. Sabendo que a maioria das cargas presentes em um sistema de distribuição é dependente dos níveis de tensão e frequência da energia de suprimento, a análise e o monitoramento dessas grandezas antes e durante o ilhamento deverão ocorrer de forma que não se perca a estabilidade da rede ilhada. Para isto, devem ser avaliadas alterações nos métodos de operação e controle dos geradores distribuídos, de maneira a atender os requisitos técnicos necessários para manter a tensão e a frequência dentro dos parâmetros de qualidade de energia elétrica. Foram propostos quatro índices de desempenho para avaliar a qualidade da energia elétrica no sistema ilhado. Os resultados obtidos demonstram a necessidade de efetuar ações corretivas eficientes para manter o sistema elétrico ilhado operando dentro dos padrões aceitáveis de qualidade de energia elétrica. Foram investigadas soluções potenciais e viáveis para garantir a operação da ilha estável e com qualidade da energia elétrica. Além disso, observou-se que cargas dependentes da tensão podem influenciar significativamente a capacidade do GD em formar de ilhas estáveis.
Título en inglés
Analysis of technical requirements for intentional islanding of distributed synchronous generators
Palabras clave en inglés
Distributed generation
Islanding
Load shedding
Power quality
Synchronous generator
Resumen en inglés
If disturbances occur in a power distribution systems in the presence of distributed generators (DGs), a common practice required by utilities is to disconnect such generators, aiming at avoiding a self-sustained energized island. This procedure is required on order to prevent damage to the whole distribution system, mainly the DG, and to the utility maintenance personnel, as well. However, this requirement may decrease the possible contributions of the distributed generation concepts to the quality of the power supply. In this context, this work aims at analyzing the technical requirements related to make DGs islanded operation feasible. Since most of the loads are dependent on the supply voltage and frequency, the analysis and monitoring of such quantities before and after an islanding event should occur in such a way that the stability of the energized island is granted. To reach such a goal, changes in the DG control modes must be assessed, so that the technical requirements necessary to keep voltage and frequency within statutory limits are fulfilled. Four performance indices have been proposed to assess the power quality in the islanded system. The results have shown the need to perform efficient corrective actions to ensure reliable islanded operation. Moreover, it was observed that voltage-dependent loads may influence the DG capability to sustain stable islands.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Rogerio.pdf (1.10 Mbytes)
Fecha de Publicación
2013-10-16
 
ADVERTENCIA: El material descrito abajo se refiere a los trabajos derivados de esta tesis o disertación. El contenido de estos documentos es responsabilidad del autor de la tesis o disertación.
  • LIMA, Rogério Lúcio; VIEIRA, José Carlos Melo. Performance Indices for Assessing the Power Quality of Islanded Operation of Distributed Generators. Journal of Control, Automation and Electrical Systems, v. 32, n. 3, p. 747-755, 2021.