Disertación de Maestría
DOI
https://doi.org/10.11606/D.18.2006.tde-05022007-110208
Documento
Autor
Nombre completo
Érico Masiero
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2006
Director
Tribunal
Vecchia, Francisco Arthur da Silva (Presidente)
Roma, Woodrow Nelson Lopes
Romero, Marcelo de Andrade
Título en portugués
Resfriamento evaporativo e condicionamento de ar convencional: estudo experimental comparativo
Palabras clave en portugués
Conforto ambiental
Eficiência energética de edifícios
Resfriamento evaporativo
Resumen en portugués
Este trabalho visa comparar experimentalmente a técnica de resfriamento evaporativo e o condicionamento de ar convencional em relação ao índice de umidificação, à redução da temperatura interna do ar e ao consumo energético. O experimento foi realizado em três células de teste submetidas às mesmas condições climáticas, semelhantes em relação às suas características construtivas e ao volume de ar interno. Cada equipamento foi instalado em uma célula, sendo que a célula restante não contou com qualquer sistema de resfriamento, cumprindo, assim, o papel de padrão de referência do comportamento higrotérmico. A técnica de resfriamento evaporativo consiste em um dispositivo eletromecânico de ventilação forçada que insufla o ar para dentro do ambiente, fazendo-o passar por um filtro de celulose umedecido com água corrente. A ventilação forçada espalha gotículas de água no ambiente interno e o contato da água com o ar quente e seco acelera a sua evaporação. Dessa forma, o ar cede calor sensível e as gotículas de água evaporam. Como conseqüência, a temperatura diminui e a umidade do ar aumenta no interior do ambiente. O condicionador de ar convencional, constituído por evaporador, compressor e condensador, refrigera o ar por meio da compressão e da expansão do gás freon. Os dados do interior de cada célula foram automaticamente coletados por meio do Datalogger Campbell Scientific Inc CR10X. As temperaturas de bulbo seco e úmido foram regitradas com sensores termopares tipo T (Cobre-Constantan). A técnica de resfriamento evaporativo atingiu índices adequados de conforto ambiental em períodos de climas quente e seco, demonstrando, assim, ser eficaz em promover a diminuição da temperatura e a umidificação de ambientes internos. Este trabalho sugere, portanto, que a técnica de resfriamento evaporativo pode ser uma alternativa para melhorar as condições térmicas dos espaços de permanência humana com consumo de energia inferior ao do condicionador de ar convencional.
Título en inglés
Evaporative cooling and conventional air conditioning: a comparative experimental study
Palabras clave en inglés
Energetic efficiency in buildings
Environmental comfort
Evaporative cooling
Resumen en inglés
This experimental research aims to compare the evaporative cooling with the conventional air conditioning in terms of levels of humidity, reduction in indoor air temperature, and energy consume. The experiment was conducted in three purpose-built test cells, similar in structure, which were exposed to the same climatic conditions and showed the same indoor air volume rates. Each equipment was installed in one of the test cells, and the remaining cell had no cooling appliances, thus being used as reference standard. The evaporative cooling technique consists of an electrical-mechanical system of forced ventilation which introduces outdoor air into the indoor environment, across a humidifier pad made of cellulose. The forced ventilation spread small drops of water into the indoor environment and the water’s contact with the dry-warm air accelerates the evaporation process. Thus, the air loses sensible heat and the water evaporates. As a result, the air temperature decreases, and the relative humidity increases inside the environment. The conventional air conditioning system, comprises of an evaporator, a compressor and a condenser, cools the air by compressing and expanding Freon gas. The data from each cell was automatically collected by using a Datalogger CR10X. Both dry and wet bulb temperature was measured by using thermocouples type T (Copper-Constantan). The evaporative cooling technique was shown to provide higher levels of human comfort during warm-dry climate, thereby demonstrating that it can be effective in humidifying and constantly replenishing indoor air. This work therefore suggests that the evaporative cooling can be an alternative for improving the conditions of purpose-built environments with lower levels of energy consume when compared with the conventional air-conditioning systems.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
RESF_EVAP2006.pdf (11.17 Mbytes)