Disertación de Maestría
DOI
https://doi.org/10.11606/D.18.2016.tde-24082016-102537
Documento
Autor
Nombre completo
Pio Antonio de Figueiredo
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2004
Director
Tribunal
Coury, Denis Vinicius (Presidente)
Marques, Paulo Mazzoncini de Azevedo
Rodrigues, José Francisco
Título en portugués
Análise da qualidade da energia em um sistema elétrico de distribuição
Palabras clave en portugués
Afundamento e elevação de tensão
Oscilação transitória
Qualidade da energia
Transformada rápida de Fourier janelada
Resumen en portugués
O trabalho ressalta a importância do tema Qualidade da Energia (QE) e apresenta alguns dos diversos distúrbios responsáveis pelo seu comprometimento. Tais distúrbios, quando presentes em um dado sistema elétrico, podem causar sérios danos tanto aos equipamentos de medição e controle pertencentes ao fornecedor de energia, como também aos equipamentos mais sensíveis pertencentes aos usuários deste sistema. Os fenômenos mais freqüentes no estudo da QE foram destacados, bem como suas definições. Conhecidos estes fenômenos, implementou-se um algoritmo computacional, utilizando como ferramenta a transformada rápida de Fourier janelada (Windowed Fast Fourier Transform - WFFT) - TRFJ, para identificar e classificar estas perturbações em um dado sistema elétrico de distribuição. Para que o resultado fosse o mais próximo possível de uma situação real, utilizou-se para análise, um sistema elétrico real de distribuição da CPFL (Companhia Paulista de Força e Luz). Sobre o referido sistema elétrico foram simulados casos de afundamentos, elevações e oscilações de tensão, criando assim, um banco de dados para, posteriormente, podermos testar e validar o algoritmo computacional implementado, na identificação destes fenômenos. Este algoritmo permite variarmos tanto o tamanho da janela, quanto a freqüência amostral do sinal. Neste estudo em particular, utilizamos tamanhos de janelas de 1 ciclo e 1/2 ciclo, e freqüência amostral do sinal, de 7,68 kHz (inicialmente utilizada para obtenção do banco de dados), e 0,769 kHz, aproximadamente. Como resultados, obtivemos que o tamanho da janela de dados para esta implementação, não apresentou diferenças significativas na análise, quando comparados com os dados iniciais. Entretanto, observa-se um comportamento contrário com a variação da taxa amostral, ou seja, quanto menor a freqüência amostral empregada, maior a perda de informações importantes em relação ao sinal inicial.
Título en inglés
Power quality analysis in an electrical system distribution
Palabras clave en inglés
Oscillatory transient
Power quality
Voltage sag
Voltage swell
Windowed fast Fourier transform
Resumen en inglés
The present work at lines the importance of Power Quality (PQ) and it presents some of the many disturbances related to it and its implications. Such disturbances, as presented in an electrical system, can cause serious damages in the measurements, in the control of power utility equipments, as well as in sensitive equipments. The most frequent phenomena in the study of PQ had been emphasized, as well as its definitions. Once these phenomena are known, a computational algorithm was implemented, using the Windowed Fast Fourier Transform - WFFT as a tool to identify and classify these disturbances, considering electrical distribution system. In order to have the best situation for the test, a real electrical distribution system from CPFL (Companhia Paulista de Força e Luz) utility was simulated. Some cases of voltage sag, voltage swell and oscillatory transient were simulated, creating a data base to test and validate the computational algorithm implemented. This algorithm allows changing the window length as the sample rate. For the proposed study, 1 cycle and 1/2 cycle as window length was analyzed with sample rate of 7,68 kHz (initially used for obtaining the data base), and 0,769 kHz. It was observed that the window length studied did not influence significantly the proposed analysis concerning PQ. However, concerning the sample rate, it was observed a deterioration of the analysis with the 0,769 kHz rate.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2016-08-24
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.