Título em português
O modelo SLIM ("Self-Consistently Interception Model") para estimativa da incidência de descargas atmosféricas em estruturas - avaliação e aplicação na análise do desempenho de linhas de transmissão de energia
Palavras-chave em português
descargas atmosféricas
distância de atração
interrupções
linhas de transmissão
Resumo em português
O desempenho de uma linha de transmissão de energia está diretamente ligado ao número médio anual de descargas que nela incidem, o qual depende da densidade média de descargas ao solo na região e também do grau de exposição da linha. Modelos com diferentes graus de complexidade são encontrados na literatura para a estimativa da área de atração de estruturas a descargas atmosféricas. Entretanto, além das grandes simplificações sobre a física das descargas nas quais a maioria desses modelos se baseia, até recentemente não era possível considerar a configuração tridimensional das estruturas. Essa é uma limitação importante, pois detalhes do objeto afetam o campo elétrico e, consequentemente, o processo de formação do líder ascendente. Nesse contexto, o modelo desenvolvido em 2006 por Becerra e Cooray - SLIM ("self-consistently interception model") utiliza os conceitos mais recentes da física das descargas para a análise dos processos de formação e propagação do líder. Ao contrário dos demais modelos, o SLIM possibilita que se leve em conta a geometria tridimensional da estrutura. O modelo foi validado com base em comparações entre valores de campo elétrico para estabilização do líder em função da altura calculados e medidos em experimentos utilizando a técnica de descargas provocadas por foguetes, tendo-se obtido excelente concordância entre os resultados. Este trabalho destaca os aspectos mais importantes do SLIM e apresenta uma análise comparativa do mesmo com outros modelos bastante conhecidos, como o Modelo Eletrogeométrico, o Modelo de Eriksson e o Modelo de Rizk, além do procedimento simplificado recomendado pelo Guia IEEE Std. 1243. A análise é feita em termos da distância e do raio de atração, do número de descargas incidentes em uma linha de transmissão e do desempenho da mesma frente a descargas atmosféricas, discriminando as taxas de falhas causadas por falha de blindagem e por "backflashover".
Título em inglês
The Self-consistently Interception Model (SLIM) for estimating the lightning incidence to structures evaluation of the model and application to the analysis of lightning performance of power transmission lines
Palavras-chave em inglês
lightning
power interruptions
striking distance
transmission lines
Resumo em inglês
In general, about 20 % to 60 % of the electric power service interruptions of distribution lines are attributed to lightning. For transmission lines, a typical figure is 70 %. The appraisal of the lightning performance of a power line is related to its mean flash collection rate, which depends on the mean ground flash density of the region and on the line exposure to direct lightning strokes. Models of different degrees of complexity are found in the literature for the estimation of lightning striking distances of objects and structures. However, besides the oversimplifications of the physical nature of the lightning discharge on which most of the models are based, till recently the tridimensional structure configuration could not be considered. This is an important limitation, as edges and other details of the object affect the electric field and, consequently, the upward leader initiation. Within this context, the self-consistently interception model (SLIM) proposed in 2006 by Becerra and Cooray is state-of-the-art leader inception and propagation leader model based on the physics of leader discharges which, unlike the other existing models, enables the tridimensional geometry of the structure to be taken into account. For the validation of the model, data obtained in rocket-triggered lightning experiments were used and an excellent agreement was found between measured and calculated leader stabilization electric fields as a function of the height of the rocket. This work describes the most important aspects of the new model and presents a comparative analysis of SLIM and other well-known model such as the Electrogeometric Model (EGM), Erikssons Model, and Rizks Model, as well as the simplified procedure recommended by IEEE Std. 1243. The analysis is done in terms of the striking distance, attractive radius, and the flash collection rate of a transmission line, as well as on its lightning performance, discriminating between the failure rates caused by shielding failure and backflashover.
 
AVISO - A consulta a este documento fica condicionada na aceitação das seguintes condições de uso:
Este trabalho é somente para uso privado de atividades de pesquisa e ensino. Não é autorizada sua reprodução para quaisquer fins lucrativos. Esta reserva de direitos abrange a todos os dados do documento bem como seu conteúdo. Na utilização ou citação de partes do documento é obrigatório mencionar nome da pessoa autora do trabalho.
Data de Publicação
2012-05-29
 
AVISO: Saiba o que são os trabalhos decorrentes clicando aqui.
Todos os direitos da tese/dissertação são de seus autores
CeTI-SC/STI
Biblioteca Digital de Teses e Dissertações da USP. Copyright © 2001-2024. Todos os direitos reservados.