Master's Dissertation
DOI
https://doi.org/10.11606/D.86.2011.tde-16082011-163415
Document
Author
Full name
Sergio Ricardo Campos Bezerra
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2011
Supervisor
Committee
Kanashiro, Arnaldo Gakiya (President)
Gonçalves Junior, Luiz
Piantini, Alexandre
Title in Portuguese
Avaliação de sistemas de aterramento considerando a utilização de condutores e hastes envolvidos em concreto
Keywords in Portuguese
Aterramento elétrico
haste envolvida em concreto
malha de aterramento
resistência de terra
resistividade do solo
Abstract in Portuguese
O aterramento elétrico cumpre uma função essencial em um sistema de distribuição de energia elétrica, devendo atender, dentre vários requisitos, aqueles estabelecidos quanto aos valores de tensão de passo e de toque. Entretanto, em locais onde o solo apresenta valores elevados de resistividade, surgem dificuldades que nem sempre são superadas no sentido de obedecer às exigências citadas nas normas técnicas e especificações. Dentro deste contexto, este trabalho tem por objetivo avaliar a utilização de condutores e hastes envolvidos em concreto em sistemas de aterramento, visando à redução dos valores de resistência de terra. Inicialmente é abordada uma configuração convencional de malha de aterramento adotada por uma concessionária de energia elétrica, sendo realizados estudos de modo a verificar a influência do espaçamento e da quantidade das hastes nos valores de resistência de terra. São também consideradas modificações nas dimensões da malha e a utilização de hastes profundas e, na seqüência, são analisados os resultados de outras configurações. De modo a verificar a efetividade do uso do concreto, foram realizadas várias simulações computacionais considerando o sistema de aterramento com a utilização de condutores e hastes envolvidos em concreto. Diversas situações foram investigadas, sendo possível concluir que o uso do concreto resulta em menores valores de resistência de terra em relação às malhas convencionais. Esse resultado, de certo modo, vem ao encontro das expectativas, porém deve ser ressaltada a contribuição do trabalho, a qual possibilita a análise, através de cálculos teóricos, do comportamento das malhas de aterramento com o uso do concreto. A literatura pesquisada apresenta poucos resultados teóricos, sendo encontradas algumas investigações nesse tema onde são consideradas somente medições realizadas no campo.
Title in English
Evaluation of grounding systems considering the use of conductors and rods encased in concrete
Keywords in English
Electrical grounding
grounding grid
grounding resistance
rods encased in concrete
soil resistivity
Abstract in English
The electrical grounding plays an essential role in a system of electric power distribution, and must follow, among many requirements, those ones established as step voltage values and touch voltage values. However, in those places where the soil has high resistivity values, some difficulties arise and may not always be overcomed in order to follow the requirements set forth in technical standards and specifications. In this context, the aim of this study is to evaluate the use of electrical conductors and rods encased in concrete inside grounding systems, in order to reduce the ground resistance values. Initially it was observed a conventional configuration of grounding grid that is used by an electric utility, and studies were made in order to verify the influence of the number of rods and the distance between them in the values of grounding resistance. There are also been taken into consideration the changes in the grounding grid dimensions and the use of deep rods and, right after, the results of other configurations are analyzed. In order to verify the effectiveness of the use of concrete, several computer simulations were performed considering the grounding system that used conductors and rods encased in concrete. Several situations were investigated, and it was possible to conclude that the use of concrete results in lower values of ground resistance compared to conventional grounding grid. This result, in a certain way, matches with the expectations, but it should be emphasized the contribution of the study which enables, through theoretical calculations, the analysis of the grounding grid behavior with the use of concrete. The literature shows few theoretical results and presents only some researches on this issue in which ones only measurements made in the field are considered.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
DissertSergio.pdf (2.38 Mbytes)