Dissertação de Mestrado
DOI
https://doi.org/10.11606/D.86.2011.tde-16082011-163415
Documento
Autor
Nome completo
Sergio Ricardo Campos Bezerra
E-mail
Unidade da USP
Área do Conhecimento
Data de Defesa
Imprenta
São Paulo, 2011
Orientador
Banca examinadora
Kanashiro, Arnaldo Gakiya (Presidente)
Gonçalves Junior, Luiz
Piantini, Alexandre
Título em português
Avaliação de sistemas de aterramento considerando a utilização de condutores e hastes envolvidos em concreto
Palavras-chave em português
Aterramento elétrico
haste envolvida em concreto
malha de aterramento
resistência de terra
resistividade do solo
Resumo em português
O aterramento elétrico cumpre uma função essencial em um sistema de distribuição de energia elétrica, devendo atender, dentre vários requisitos, aqueles estabelecidos quanto aos valores de tensão de passo e de toque. Entretanto, em locais onde o solo apresenta valores elevados de resistividade, surgem dificuldades que nem sempre são superadas no sentido de obedecer às exigências citadas nas normas técnicas e especificações. Dentro deste contexto, este trabalho tem por objetivo avaliar a utilização de condutores e hastes envolvidos em concreto em sistemas de aterramento, visando à redução dos valores de resistência de terra. Inicialmente é abordada uma configuração convencional de malha de aterramento adotada por uma concessionária de energia elétrica, sendo realizados estudos de modo a verificar a influência do espaçamento e da quantidade das hastes nos valores de resistência de terra. São também consideradas modificações nas dimensões da malha e a utilização de hastes profundas e, na seqüência, são analisados os resultados de outras configurações. De modo a verificar a efetividade do uso do concreto, foram realizadas várias simulações computacionais considerando o sistema de aterramento com a utilização de condutores e hastes envolvidos em concreto. Diversas situações foram investigadas, sendo possível concluir que o uso do concreto resulta em menores valores de resistência de terra em relação às malhas convencionais. Esse resultado, de certo modo, vem ao encontro das expectativas, porém deve ser ressaltada a contribuição do trabalho, a qual possibilita a análise, através de cálculos teóricos, do comportamento das malhas de aterramento com o uso do concreto. A literatura pesquisada apresenta poucos resultados teóricos, sendo encontradas algumas investigações nesse tema onde são consideradas somente medições realizadas no campo.
Título em inglês
Evaluation of grounding systems considering the use of conductors and rods encased in concrete
Palavras-chave em inglês
Electrical grounding
grounding grid
grounding resistance
rods encased in concrete
soil resistivity
Resumo em inglês
The electrical grounding plays an essential role in a system of electric power distribution, and must follow, among many requirements, those ones established as step voltage values and touch voltage values. However, in those places where the soil has high resistivity values, some difficulties arise and may not always be overcomed in order to follow the requirements set forth in technical standards and specifications. In this context, the aim of this study is to evaluate the use of electrical conductors and rods encased in concrete inside grounding systems, in order to reduce the ground resistance values. Initially it was observed a conventional configuration of grounding grid that is used by an electric utility, and studies were made in order to verify the influence of the number of rods and the distance between them in the values of grounding resistance. There are also been taken into consideration the changes in the grounding grid dimensions and the use of deep rods and, right after, the results of other configurations are analyzed. In order to verify the effectiveness of the use of concrete, several computer simulations were performed considering the grounding system that used conductors and rods encased in concrete. Several situations were investigated, and it was possible to conclude that the use of concrete results in lower values of ground resistance compared to conventional grounding grid. This result, in a certain way, matches with the expectations, but it should be emphasized the contribution of the study which enables, through theoretical calculations, the analysis of the grounding grid behavior with the use of concrete. The literature shows few theoretical results and presents only some researches on this issue in which ones only measurements made in the field are considered.
 
AVISO - A consulta a este documento fica condicionada na aceitação das seguintes condições de uso:
Este trabalho é somente para uso privado de atividades de pesquisa e ensino. Não é autorizada sua reprodução para quaisquer fins lucrativos. Esta reserva de direitos abrange a todos os dados do documento bem como seu conteúdo. Na utilização ou citação de partes do documento é obrigatório mencionar nome da pessoa autora do trabalho.
DissertSergio.pdf (2.38 Mbytes)
Data de Publicação
2011-08-29
 
AVISO: Saiba o que são os trabalhos decorrentes clicando aqui.
Todos os direitos da tese/dissertação são de seus autores
CeTI-SC/STI
Biblioteca Digital de Teses e Dissertações da USP. Copyright © 2001-2024. Todos os direitos reservados.