• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Tesis Doctoral
DOI
https://doi.org/10.11606/T.86.2013.tde-13012014-103847
Documento
Autor
Nombre completo
Marcos Eduardo Guerra Alves
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2013
Director
Tribunal
Tatizawa, Hédio (Presidente)
Altafim, Ruy Alberto Corrêa
Burani, Geraldo Francisco
Kanashiro, Arnaldo Gakiya
Santos, Josemir Coelho
Título en portugués
Metodologia para o diagnóstico em tempo real de para-raios em sistemas de distribuição e transmissão de energia elétrica
Palabras clave en portugués
Diagnóstico em tempo real
Monitoração contínua
Para-raios
Soma vetorial de correntes
Resumen en portugués
Dada a importância dos para-raios para a proteção dos diversos equipamentos e instalações nos sistemas de distribuição e transmissão de energia elétrica contra danos provocados por sobretensões transitórias, quer sejam originadas por descargas atmosféricas, quer por estabelecimento e interrupção de cargas reativas (sobretensões de manobra), é apresentada uma nova metodologia de diagnóstico de seu estado. São apresentadas também as formas construtivas dos para-raios com tecnologias de carboneto de silício (SiC) e óxido de zinco (ZnO), as quais são associadas a modelos elétricos de representação completos e simplificados, de forma a facilitar a análise dos métodos de diagnóstico. Os métodos atualmente empregados para o diagnóstico dos para-raios, tanto fora de serviço quanto durante a operação, bem como suas potencialidades e pontos falhos são explanados, para os equipamentos de SiC e de ZnO. O novo método de diagnóstico proposto nesse trabalho é introduzido a seguir, baseado na monitoração da capacitância equivalente e resistência equivalente do para-raio, juntamente com simulações dos diversos tipos de defeitos passíveis de ocorrência em equipamentos de SiC e ZnO, verificando-se os parâmetros de medição afetados por cada um deles, de forma a estabelecer a efetividade do novo método de monitoração para a detecção dos defeitos. Também é apresentado um método para viabilização da monitoração em tempo real de capacitância e de resistência equivalentes, através da técnica de soma vetorial das correntes de fuga, atualmente já empregada para monitoração de buchas capacitivas de transformadores e outros equipamentos. Por fim, são apresentados os resultados esperados com o novo método de monitoração e as sugestões de novas etapas para trabalhos futuros.
Título en inglés
Methodology for Real Time Diagnostic of Surge Arresters in Electric Energy Distribution and Transmission Systems
Palabras clave en inglés
On-line monitoring
Real time diagnostic
Surge arresters
Vector sum of currents
Resumen en inglés
Given the importance of surge arresters for the protection of several devices and installations in electric energy distribution and transmission systems from damages caused by transitory overvoltages, either originated from atmospheric discharges or by closing or opening of reactive loads (switching overvoltages), a new methodology for diagnosing their condition is presented. The constructive forms of surge arresters with silicon carbide (SiC) and zinc oxide (ZnO) technologies are presented, as well as their associated electric representation models, complete and simplified, so as to facilitate the analysis of diagnostic methods. Surge arrester diagnostic methods are presented, both off-line and on-line, together with their potentialities and weak points, for SiC and ZnO arresters. The new diagnostic method proposed in this work is introduced next, based on monitoring of the arrester equivalent capacitance and equivalent resistance, followed by simulations of the several possible defect types in SiC and ZnO devices. The measured parameters affected by each defect type are checked in order to establish the effectiveness of the new monitoring method for the detection of arrester problems. A method for making the monitoring of equivalent capacitance and resistance is also presented, by using the vector sum of leakage currents technique, largely used for monitoring of capacitive bushings in power transformers and other equipment. Finally, the results expected with the new monitoring method and suggestions for future work are presented.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2014-01-23
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.