• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Tese de Doutorado
DOI
https://doi.org/10.11606/T.86.2014.tde-05082014-140306
Documento
Autor
Nome completo
Gustavo de Andrade Barreto
E-mail
Unidade da USP
Área do Conhecimento
Data de Defesa
Imprenta
São Paulo, 2014
Orientador
Banca examinadora
Grimoni, Jose Aquiles Baesso (Presidente)
Burani, Geraldo Francisco
Dietrich, Alvaro Batista
Penteado Junior, Aderbal de Arruda
Zilles, Roberto
Título em português
Metodologia de aplicação de geração distribuída fotovoltaica em baixa tensão nos reticulados subterrâneos das distribuidoras de energia elétrica
Palavras-chave em português
distribuição de energia elétrica
geração distribuída fotovoltaica
protetores de rede
reticulado
subterrâneo
Resumo em português
O objetivo deste estudo foi a elaboração e testes simulados, com dados elétricos reais, de metodologia para a operação de geração distribuída (GD) fotovoltaica, em baixa tensão e com exportação de excedentes, em sistemas de distribuição reticulado. A metodologia superou as limitações impostas pelos equipamentos de proteção chamados Protetores de Rede, inerentes à topologia de distribuição do tipo reticulado. Tais equipamentos inviabilizam a geração distribuída, que exporta excedentes para a rede externa por desconectarem os transformadores de média para baixa tensão, causando o ilhamento da GD, sempre que existir um fluxo de potência reverso, ou seja, no sentido do cliente para a concessionária. O objetivo foi alcançado por meio da criação de um simulador de subestação de reticulado exclusivo (Spot) de três transformadores nos qual os comportamentos dos protetores de rede eram testados com dados de fluxo de potência reais aquisitados em subestações de reticulado em Brasília (concessionária CEB) e em subestação do Instituto de Energia e Ambiente (IEE), da Universidade de São Paulo, onde existe uma instalação geradora fotovoltaica de 12kWp. Novos comportamentos dos protetores de rede foram simulados para compatibilizar tal fluxo reverso de potência e parâmetros críticos foram levantados. Nas simulações, encontraram-se caminhos viáveis de promover estas conexões com segurança e simplicidade. Estes novos comportamentos podem ser implementados no firmware dos relés de protetores de redes microprocessados.
Título em inglês
Operation of Photovoltaic Distributed Generation (DG) on Secondary Side of the Spot and Grid Network Distribution Systems
Palavras-chave em inglês
network protectors
photovoltaic distributed generation
spot network
underground electricity distribution networks
Resumo em inglês
The aim of this study was to develop and test a methodology for operation of photovoltaic distributed generation (DG) on secondary side of the Spot and Grid Network types of electricity distribution systems, allowing for the export of excess energy. This methodology did overcome the limitations imposed by the protective equipment known as Network Protector (NP), a standard equipment on secondary network distribution topology. Such equipments make exporting energy from distributed generation systems to the grid unfeasible because of the operational aspects of Network Protectors. This devices will disconnect the transformers whenever there is a reverse power flow, i.e. towards the utility, causing the islanding of the DG. The objective was achieved through the conception of a simulator for a Spot Network substation with three transformers where the behaviors of network protectors could be tested. Those simulations were performed with actual power flow data from real network substations in Brasilia city (CEB utility area) and the substation at the Institute for Energy and Environment (IEE) at the University of Sao Paulo, where a photovoltaic generating facility of 12kWp exists. New behaviors were simulated in order to make the NPs to manage the expected reverse power flow successfully. The most important parameters for the model were explained. Viable ways to connect exporting photovoltaic DG to secondary networks safely and simply have been found by means of these simulations. These new behaviors could be embedded in the firmware of the NP´s microprocessor based relays.
 
AVISO - A consulta a este documento fica condicionada na aceitação das seguintes condições de uso:
Este trabalho é somente para uso privado de atividades de pesquisa e ensino. Não é autorizada sua reprodução para quaisquer fins lucrativos. Esta reserva de direitos abrange a todos os dados do documento bem como seu conteúdo. Na utilização ou citação de partes do documento é obrigatório mencionar nome da pessoa autora do trabalho.
Data de Publicação
2014-08-18
 
AVISO: Saiba o que são os trabalhos decorrentes clicando aqui.
Todos os direitos da tese/dissertação são de seus autores
CeTI-SC/STI
Biblioteca Digital de Teses e Dissertações da USP. Copyright © 2001-2024. Todos os direitos reservados.