Title in Portuguese
Modelo estrutural numérico que simula a alocação de absorvedores dinâmicos para redução de ruído acústico emitido por um transformador de potência.
Keywords in Portuguese
Dinâmica (simulações)
Método dos elementos finitos
Ruído urbano
Vibrações
Abstract in Portuguese
Os transformadores de potência elétrica produzem um elevado nível de ruído que em alguns casos gera desconforto à comunidade vizinha. O presente trabalho desenvolve um modelo estrutural de elementos nitos que, com carregamento adequado, é capaz de reproduzir o deslocamento, medido durante a operação, de um transformador de potência elétrica. Este modelo estrutural é utilizado para calcular a redução do deslocamento das superfícies deste transformador decorrentes do emprego de absorvedores dinâmicos de vibração. Este modelo estrutural foi desenvolvido para estimar o número de absorvedores dinâmicos, sua massa e sua localização que permitiria reduzir o ruído acústico emitido por este transformador de potência até alcançar níveis de intensidade de som em comformidade com a legislação brasileira.
Title in English
Numerical structural model that simulates the dynamic absorbers position to reduce acoustic noise emitted by a power transformer.
Keywords in English
Dynamic absorber
Industrial noise
Power transformer
Transformer tank
Vibrations
Abstract in English
Electrical power transformers produce a high level of noise, which, in some cases, generate discomfort to the surrounding community. The present work develops a structural model by the Finite Element Method that, with adequate loading conditions, is capable of reproducing the displacement, measured during operation, of the transformer tank. The structural model has been used to compute the displacement reduction of the transformer surfaces by using dynamic vibration absorbers. The structural model was developed to estimate the number of dynamic absorbers, the mass and localization that could reduce the acoustic noise to levels of intensity of sound in accordance to the Brazilian law.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
diser_lucho.pdf (3.52 Mbytes)
Publishing Date
2009-08-18
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.