• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Doctoral Thesis
DOI
https://doi.org/10.11606/T.3.2008.tde-29012009-141031
Document
Author
Full name
Marcelo Luiz Pereira
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2008
Supervisor
Committee
Tribess, Arlindo (President)
Assunção, João Vicente de
Graudenz, Gustavo Silveira
Güths, Saulo
Yanagihara, Jurandir Itizo
Title in Portuguese
Medição, predição e análise de partículas aéreas em salas cirúrgicas.
Keywords in Portuguese
Ar condicionado
Contaminação aérea
Qualidade do ar
Salas cirúrgicas
Abstract in Portuguese
Os sistemas de condicionamento de ar exercem função importante em uma sala cirúrgica, que é proteger a ferida cirúrgica e os equipamentos estéreis dos microrganismos carreados pelo ar. Essa proteção é feita pelo controle simultâneo da movimentação e distribuição do ar, da temperatura, da umidade, da filtragem, das infiltrações de ar de outros setores, entre outros. Esses são fatores que afetam diretamente a quantidade de partículas aéreas presentes em uma sala cirúrgica. Dentro deste contexto, no presente trabalho foi desenvolvido um modelo matemático para predição da concentração de partículas em salas cirúrgicas e para determinação da importância relativa dos fatores que interferem na geração e remoção dessas partículas. O modelo proposto baseia-se no balanço de massa para o cálculo da concentração de partículas, que foi aplicado e validado com os dados obtidos em salas cirúrgicas com diferentes tipos de sistemas de condicionamento de ar. Nessas salas cirúrgicas foram realizadas medições de variáveis ambientais considerando diferentes situações que normalmente ocorrem na rotina de salas cirúrgicas. Para cada uma das condições analisadas, é proposto um determinado conjunto de parâmetros relativos ao ambiente, ao sistema de condicionamento de ar e às concentrações de partículas provenientes das diversas fontes, que são utilizados como dados de entrada no modelo. O modelo que está sendo proposto também pode ser utilizado como uma importante ferramenta para auxiliar na análise específica dos fatores que afetam tanto a geração como a remoção de partículas.
Title in English
Measurement, prediction and analysis of airborne particles in surgical rooms.
Keywords in English
Air conditioning
Air quality
Airborne contamination
Surgical rooms
Abstract in English
Air conditioning systems exert an important function in surgical rooms, to protect the surgical wound and the sterile equipments from airborne infected particles. This protection is achieved by means of a simultaneous control of the movement and distribution of the air, of the temperature, of the humidity, of the filtering, of air infiltrations from other sections etc. Those factors directly affect the amount of airborne particles present in a surgical room. Within this context, the present work aimed to develop a mathematical model for the prediction of particle concentrations in surgical rooms and for the determination of the relative importance of the factors that interfere in the generation and removal of those particles. The proposed model, based on mass balance for the calculation of the particle concentrations, has been applied and validated with the data obtained from different types of air conditioning systems in which the measurements were carried out, as well as with different conditions that commonly occur in the routine of surgical rooms. For each one of these conditions, a certain group of relative parameters is proposed to the environment, to the air conditioning system, and to the concentrations of particles originated from the different sources, which are used as input data to the model. The proposed model can also be used as an important tool to aid in the specific analysis of the factors that affect both particle generation and removal.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2009-02-06
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.