Estudo da qualidade do ar interior em ambientes educacionais.
Keywords in Portuguese
Ambientes fechados
Ar condicionado
Poluição atmosférica
Ventilação
Abstract in Portuguese
A Qualidade do Ambiente Interior (QAI) é um dos principais fatores que determina a funcionalidade, harmonia, conforto e produtividade em um edifício. A QAI afeta a saúde e o conforto dos ocupantes de um edifício, bem como a habilidade dos mesmos em realizar tarefas, influenciando diretamente na produtividade. Quando a QAI é boa, os ambientes se tornam lugares mais desejáveis para estar, trabalhar e aprender. O ambiente de escolas e universidades pode exercer um impacto significativo na saúde e no aprendizado de crianças e estudantes universitários. A limitação da entrada de poluentes e contaminantes, bem como o fornecimento da quantidade adequada de ar externo filtrado e limpo, melhoram o desempenho acadêmico dos estudantes e não atinge a saúde dos mesmos. Este trabalho apresenta medições de parâmetros físicos e químicos, CO2, PM2,5, PM10, temperatura de bulbo seco e umidade relativa, efetuadas em uma sala de aula do prédio de Engenharia Mecânica da Escola Politécnica da Universidade de São Paulo (EPUSP) os quais os estudantes e professores estavam sujeitos. As medidas foram tomadas no ambiente interno e externo a sala de aula, onde atividades teóricas e práticas eram realizadas. A vazão de ar externo, previamente filtrado, era variada para a redução dos contaminantes gerados internamente. Constatou-se que os particulados PM2,5 e PM10 atingiram concentrações críticas de 6 e 30 vezes maiores do que o limite proposto pelas normas vigentes, respectivamente, bem como a concentração de CO2 que atingiu 3 vezes o limite recomendado. Porém, observou-se que o aumento da vazão de ar externo em aproximadamente 2200 m³/h foi suficiente para a diminuição da concentração de PM10 em 50% nos primeiros 20 minutos. Apesar da diminuição da concentração, a vazão recomendada de ar externo por pessoa não foi suficiente para a concentração de material particulado atingir os limites aceitáveis. Por fim, apresenta-se uma proposta de projeto detalhado de dois sistemas independentes de tratamento de ar que permitirão a realização de experimentos e estudos sobre a QAI, podendo-se variar a vazão de ar externo e a classe de filtragem da recirculação e da tomada de ar externo para dois laboratórios do Departamento de Engenharia Mecânica da EPUSP, que podem dar sequência aos estudos deste trabalho.
Title in English
Study of indoor air quality in educational environments.
Keywords in English
Air conditioning
Air pollution
Educational environments
Indoor environmental quality
Ventilation
Abstract in English
The Indoor Environmental Quality (IEQ) is one of the main factors that determines the functionality, harmony, comfort and productivity in a building. The IEQ affects the health and comfort of the occupants of a building, as well as the ability of them to perform tasks, influencing directly in productivity. When IEQ is good, the environments become more desirable places to be in, work and learn. The indoor environment of schools and universities can have a significant impact on the health and learning of children and college students. The limitation of input of pollutants and contaminants, as well as providing the appropriate amount of filtered and clean outside air, improve the academic performance of students and does not affect the health of the same. This paper presents measurements of physical and chemical parameters, CO2, PM2,5, PM10, dry bulb temperature and relative humidity, made in a classroom of the Mechanical Engineering building of the Polytechnic School of the University of São Paulo (EPUSP) which students and teachers were subject. The measurements were taken in the internal and external environment of the classroom, where theoretical and practical activities were conducted. The flow of outside air, previously filtered, was varied for the reduction of contaminants generated internally. It was found that the particulate PM2,5 and PM10 achieved critical concentrations of 6 and 30 times greater than the limit proposed by the current standards, respectively, and that the concentration of CO2 reached 3 times the recommended limit. However, it was observed that increasing outside air flow of approximately 2200 m³/h was enough to decrease the concentration of PM10 in 50% at the first 20 minutes. Despite the decreased concentration, the recommended flow of outside air per person was not enough for the concentration of particulate matter reaches the acceptable limits. Finally, a detailed project proposal is presented of two independent air treatment systems that will allow performing experiments and studies on the IEQ, being able to vary the flow of outside air and, the filters of the recirculation and external air intake for two laboratories of the Department of Mechanical Engineering of EPUSP, that can follow the studies of this work.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2017-07-12
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.