Master's Dissertation
DOI
https://doi.org/10.11606/D.3.2016.tde-20072016-143140
Document
Author
Full name
Rodrigo de Oliveira Marques
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2015
Supervisor
Committee
Ferreira Filho, Sidney Seckler (President)
Mendes, Carlos Gomes da Nave
Piveli, Roque Passos
Title in Portuguese
Cinética de floculação de água bruta com baixa turbidez utilizando sais de alumínio e ferro como coagulante.
Keywords in Portuguese
Cianobactéria
Cinética
Cloreto férrico
Coagulação
Floculação
Sulfato de alumínio
Tratamento de água
Abstract in Portuguese
Este trabalho teve como propósito investigar a cinética de floculação de água bruta com baixa turbidez, utilizando o sulfato de alumínio (Al2(SO4)3o18H2O) e o cloreto férrico (FeCl3o6H2O) como coagulantes. Os resultados experimentais foram obtidos em ensaios de "jar test". A água bruta utilizada nos ensaios foi preparada em laboratório, simulando um manancial superficial eutrofizado contendo células da cianobactéria Microcystis aeruginosa. Foram testadas 5 dosagens distintas de cada coagulante, 3 valores de G, 2 valores de TAS e 12 tempos de floculação. Utilizou-se a turbidez como medida principal de avaliação dos resultados experimentais. O valor de turbidez inicial (N0) foi corrigido, levando-se em consideração o acréscimo de turbidez em função das dosagens de coagulante. Determinou-se que as dosagens mais efetivas, em termos de remoção de turbidez, foram 20 mg.L-1 para o sulfato de alumínio e 40 mg.L-1 para o cloreto férrico (ambas expressas como massa de coagulante). Para ambos os coagulantes, constatou-se que G = 20 s-1 e TAS = 27 m3.m-2.dia-1 resultaram nas melhores eficiências de remoção de turbidez. Verificou-se também a variação do potencial zeta em função das dosagens de coagulante. Observou-se que o aumento da dosagem de coagulante leva à redução do potencial zeta, aproximando-o do ponto isoelétrico. Porém, o ponto isoelétrico não necessariamente coincide com a melhor eficiência em termos de remoção de turbidez. Com base nos resultados experimentais, foi proposta uma modificação ao modelo clássico da cinética de floculação de suspensões coloidais. Nesta, foi incluso um segundo termo referente à ruptura de flocos (quebra irreversível). O ajuste do modelo proposto foi obtido através de procedimentos de iteração numérica computacional com a função "Solver" do programa Microsoft Excel®. Foram calculados os valores das constantes KA, KB e KC do modelo proposto. Amostras do lodo gerado nos ensaios de cinética de floculação foram caracterizadas visualmente através de microscopia eletrônica de varredura (MEV).
Title in English
Flocculation kinetics of low-turbidity raw water using aluminum and iron salts as coagulants.
Keywords in English
Aluminum sulfate
cyanobacteria
Ferric chloride
Flocculation
Kinetics
Abstract in English
The purpose of this work was to investigate flocculation kinetics of low-turbidity raw water, using aluminum sulfate (Al2(SO4)3o18H2O) and ferric chloride (FeCl3o6H2O) as coagulants. Experimental results were obtained in jar tests. Raw water used in the jar tests was prepared in laboratory, simulating a eutrophic natural water source containing cells of the cyanobacteria Microcystis aeruginosa. 5 different coagulant doses were tested for each coagulant, 3 G values, 2 SLR values and 12 flocculation times. Turbidity was selected as the major parameter for experimental results analysis. Initial turbidity values (N0) were corrected taking into account turbidity increase due to coagulant dosing. In terms of turbidity removal, it was determined that the most effective dosage for aluminum sulfate was 20 mg.L-1, and for ferric chloride, 40 mg.L-1 (both expressed as coagulant mass). For both coagulants, it was found that G = 20 s-1 and SLR = 27 m3.m-2.day-1 resulted in the best turbidity removal efficiencies. Zeta potential variation, due to coagulant dosing, was also verified. It was noted that increasing coagulant dosing led to zeta potential reduction, bringing it closer to the isoelectric point. However, the isoelectric point does not necessary coincides with the best turbidity removal efficiency. Based on the experimental results, it was proposed a modification to the classic colloidal suspension flocculation kinetics model. In this modification, a second term regarding floc rupture (irreversible breakage) was included. Through computer numeric iteration using Microsoft Excel®'s "Solver" function, the proposed model adjustment was obtained. Kinetics constants KA, KB e KC values, from the proposed model, were calculated. Sludge samples, generated during flocculation kinetics tests, were visually characterized through scanning electronic microscopy (SEM).
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2016-07-21
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.