Master's Dissertation
DOI
https://doi.org/10.11606/D.3.2006.tde-13032007-011128
Document
Author
Full name
Breno Botelho Ferraz do Amaral Gurgel
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2006
Supervisor
Committee
Tsutiya, Milton Tomoyuki (President)
Além Sobrinho, Pedro
Helou, Luiz Carlos
Title in Portuguese
Proposição de uma metodologia para avaliação de inversores de freqüência em estações elevatórias de água: estudo de casos no sistema de abastecimento de água de São José dos Campos.
Keywords in Portuguese
Bombas centrífugas
Estações elevatórias
Inversores de freqüência
Motores elétricos
Abstract in Portuguese
Este trabalho avalia a aplicação de inversores de freqüência realizada em estações elevatórias de água tratada da cidade de São José dos Campos que são monitoradas pelo Centro de Controle Operacional da Sabesp. Foram estudadas as características técnicas de quatro sistemas de bombeamento que operam com velocidade variável. O trabalho apresenta uma proposta de metodologia para a seleção de inversores de freqüência, com base na metodologia recomendada pelo EUROPUMP e HYDRAULIC INSTITUTE (2004) aplicada em quatro sistemas da cidade de São José dos Campos. Essa proposta de metodologia foi executada através da avaliação seqüencial de um fluxograma e da análise gráfica das informações instantâneas e históricas dos parâmetros de vazão, pressão e freqüência de rotação, existentes no banco de dados dos servidores de supervisão e controle do Centro de Controle Operacional de São José dos Campos. Após a aplicação dessa metodologia, conclui-se que, a aplicação de inversores de freqüência nos sistemas estudados estava adequada e recomenda-se a sua aplicação em sistemas de bombeamento semelhantes.
Title in English
Proposal of methodology to evaluation of variable frequency drives in water pumping stations: case study in water supply system in the city of São José dos Campos.
Keywords in English
Centrifugal pumps
Electric motors
Pumping stations
Variable frequency drives
Abstract in English
The main purpose of this work is to evaluate the application of Variable Frequency Drives ? VFD, carried out in water pumping stations managed by SABESP ? Companhia de Saneamento Básico do Estado de São Paulo, located in the city of Sâo José dos Campos that are monitored by the Operational Control Center ? O.C.C. Technical characteristics of four pumping systems were studied, mainly those operating with fixed or changeable speed. It proposes a new methodology for VFD selection, based on the methodology recommended by EUROPUMP and HYDRAULIC INSTITUTE (2004), used on the systems mentioned before. This proposal of methodology were done using instantaneous and historical information of flow, pressure and rotation frequency parameters stored on data base installed on supervision and control servers installed. After this application, we also concluded that the use of VFD on the evaluated systems was correct and through this we recommend its use on similar pumping systems.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2007-03-13
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.