Master's Dissertation
DOI
https://doi.org/10.11606/D.3.2010.tde-27052010-140526
Document
Author
Full name
Silvio Giuseppe Di Santo
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2010
Supervisor
Committee
Pereira, Carlos Eduardo de Morais (President)
Coury, Denis Vinicius
Manassero Junior, Giovanni
Title in Portuguese
Localização de faltas em linhas de transmissão com múltiplas derivações utilizando dados de somente dois terminais.
Keywords in Portuguese
Linhas de transmissão de energia elétrica
Proteção de sistemas elétricos
Sistemas elétricos de potência
Abstract in Portuguese
Neste trabalho foi desenvolvido um método de localização de faltas em linhas de transmissão constituídas de circuito simples e continuamente transpostas com derivações. Este método utiliza fasores de tensão e corrente pré-falta e pós-falta medidos apenas nos terminais local e remoto, para determinar as informações da falta, as quais são: local, distância, resistência e tipo. O método de localização de faltas proposto neste trabalho é composto pelo processo de obtenção dos fasores, pelo algoritmo de determinação do tipo de falta, pelos algoritmos de estimativa de cargas e de localização de faltas, onde o algoritmo de localização de faltas foi proposto neste trabalho. A principal característica deste novo método é a de não haver necessidade de reduzir a linha para uma linha equivalente de dois terminais para aplicação do método de localização de faltas usando dados de um ou dois terminais para determinar o possível ou os possíveis locais de ocorrência da falta, uma vez que o algoritmo de localização de faltas proposto neste trabalho possui uma função objetivo que determina de forma direta o trecho de ocorrência da falta. Com o objetivo de avaliar a eficiência do método de localização de faltas proposto, este foi submetido a simulações de variação de distância de falta, de resistência de falta, de tipo de falta e simulações de erros nos fasores e nos parâmetros da linha de transmissão.
Title in English
Multiterminal transmission line fault location method using only two terminals data.
Keywords in English
Electric energy transmission line
Electric power system
Power system relaying
Abstract in English
In this work was developed a fault location method on single circuit continuously transposed transmission lines with derivations. This method uses pre-fault and post-fault voltage and current phasors, measured at local and remote terminals only, to determine the information about the fault, which are: location, distance, resistance and type. The fault location method proposed in this work is composed by the phasor obtaining process, the fault type determination algorithm, the load estimation algorithm and the fault location algorithm, where the fault location algorithm has been proposed in this work. The main characteristic of this new method is no need to reduce the line to two terminals equivalent line to application of the one or two terminal fault location method which determine the possible fault location occurrence, since the fault location algorithm proposed in this work has an objective function that determines by direct way the exact path of fault occurrence. In order to evaluate the efficiency of the proposed fault location method, it was subjected to fault distance, fault resistance and fault type variation simulations and phasors and transmission lines parameters errors simulations.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2010-11-26
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.