Disertación de Maestría
DOI
https://doi.org/10.11606/D.3.2016.tde-20062016-083241
Documento
Autor
Nombre completo
Danilo Augusto Salgado
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2015
Director
Tribunal
Kagan, Nelson (Presidente)
Almeida, Carlos Frederico Meschini
Freitas Filho, Walmir de
Título en portugués
Uma abordagem paramétrica do impacto da geração distribuída sobre as correntes de curto-circuito e na proteção de redes de distribuição.
Palabras clave en portugués
Análise paramétrica
Correntes de curto-circuito
Distribuição de energia elétrica
Geração distribuída de energia elétrica
Resumen en portugués
Esta dissertação tem por propósito analisar os impactos da geração distribuída sobre as correntes de curto-circuito e sobre a proteção das redes de média tensão das concessionárias de distribuição de energia elétrica usando uma abordagem paramétrica. A principal motivação deste trabalho são os recentes incentivos regulatórios que estão fomentando a geração distribuída no Brasil. Contudo, as redes de distribuição convencionais foram projetadas para serem passivas e a introdução da geração poderá causar problemas de ordem técnica que ainda precisam ser resolvidos. Tais problemas foram pesquisados e aqueles relacionados com os impactos sobre as correntes de curto-circuito foram enfatizados. As normas técnicas das concessionárias também foram investigadas porque seus requisitos, como a ligação dos transformadores de acoplamento, influem nas correntes de curto-circuito. Para se calcular as correntes de curto-circuito, desenvolveu-se uma planilha eletrônica cujos resultados foram validados com programas comerciais de análise de redes elétricas. Esta ferramenta foi utilizada para demonstrar, através de exemplos, o impacto causado pela geração distribuída sobre as correntes de curto-circuito e, posteriormente, para realizar as análises paramétricas nas quais a influência de cada variável foi avaliada. A aplicação do método paramétrico permitiu o estudo de possíveis limites para a potência de um gerador distribuído em função dos impactos admissíveis, de seu ponto de conexão, de seus parâmetros elétricos e dos parâmetros elétricos da rede.
Título en inglés
A parametric approach to the impacts of distributed generation on the short-circuit currents and the protection of distribution networks.
Palabras clave en inglés
Distributed generation
Electric power distribution
Parametric analysis
Short-circuit currents
Resumen en inglés
The purpose of this thesis is to analyse the impacts of distributed generation on short-circuit currents and protection of the distribution utilities medium voltage networks using a parametric approach. The new regulations that are promoting the distributed generation in Brazil are the main motivation for this work. However, the conventional distribution networks were designed to be passive; therefore the integration of generation may cause some technical problems yet to be solved. Such problems were researched and those related to the impacts on short-circuit currents were emphasized. The utilities technical standards were also explored as their requirements affect the short-circuit currents (e.g. the transformers connections). A spreadsheet was developed in order to calculated the short-circuit currents and it was validated comparing its results to those of a commercial network analysis software. This tool was used to expose the impacts of distributed generation on short-circuit currents through examples and also to carry out parametric analysis in which the influence of every variable was evaluated. The application of a parametric method made it possible to define the maximum installed capacity of a distributed generator as a function of the allowed limits to the impacts on the short-circuit currents, its point of coupling, its electrical parameters and the electrical parameters of the network.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.