Mémoire de Maîtrise
DOI
https://doi.org/10.11606/D.3.2012.tde-15072013-154428
Document
Auteur
Nom complet
Alex Almeida Pignatti
Adresse Mail
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Paulo, 2012
Directeur
Jury
Schmidt, Hernán Prieto (Président)
Ahn, Se Un
Kagan, Nelson
Titre en portugais
O impacto da topologia de conexão de transdutores na obtenção de indicadores de qualidade de energia.
Mots-clés en portugais
Distorção harmônica
Medição
Qualidade de energia
Transdutor
Resumé en portugais
A Agência Nacional de Energia Elétrica (ANEEL) deverá estabelecer a regulamentação para distúrbios de qualidade de energia em um futuro próximo. Há ainda questões em aberto sobre os procedimentos de medição e limites máximos para os indicadores de qualidade de energia. Este trabalho aborda uma dessas questões, que é a conexão de transdutores e os impactos nos índices de qualidade de energia associados. Simulações em ATPDraw e campanhas de medição foram realizadas de modo a identificar o comportamento dos indicadores de distorção harmónica sob as duas configurações possíveis de conexão de transdutores: dois equipamentos com ligação entre fases ou três com ligação fase-neutro. Os resultados das simulações e os valores medidos mostram grandes discrepâncias entre ambas as configurações, e as diferenças tornam-se ainda mais significativas com o incremento do desequilíbrio do sistema elétrico. As causas subjacentes deste fenômeno são investigadas e discutidas
Titre en anglais
The impact of transducers conection type in power quality measurements.
Mots-clés en anglais
Harmonic distortion
Measurement
Power quality
Transducer
Resumé en anglais
The Brazilian electricity regulatory agency (ANEEL) is expected to establish a legal framework for quality disturbances in the near future. There are still some open questions regarding metering procedures and maximum limits for Power Quality indicators. This work addresses one of such issues, namely the connection of the associated transducers and its impact on PQ indexes. Simulations in ATPDraw and on-field measurement campaigns were carried out so as to identify the behavior of harmonic distortion indicators under the two possible transducer configurations: two phase-to-phase or three phase-to-neutral transducers. Simulation results and measured values show large discrepancies between both configurations, and the differences become more significant as the electrical systems unbalance increases. The underlying causes of this phenomenon are investigated and discussed.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Date de Publication
2013-07-19
 
AVERTISSEMENT: Le matériau se réfère à des documents provenant de cette thèse ou mémoire. Le contenu de ces documents est la responsabilité de l'auteur de la thèse ou mémoire.
  • PIGNATTI, A. A., AHN, Se Un, e Schmidt, H.P. Impacto da conexão dos transdutores nas medições de Qualidade de Energia. In IX Conferência Brasileira Sobre Qualidade da Energia Elétrica, Cuiabá, 2011. IX Conferência Brasileira Sobre Qualidade da Energia Elétrica., 2011.
Tous droits de la thèse/dissertation appartiennent aux auteurs