• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Master's Dissertation
DOI
https://doi.org/10.11606/D.3.2012.tde-15072013-154428
Document
Author
Full name
Alex Almeida Pignatti
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2012
Supervisor
Committee
Schmidt, Hernán Prieto (President)
Ahn, Se Un
Kagan, Nelson
Title in Portuguese
O impacto da topologia de conexão de transdutores na obtenção de indicadores de qualidade de energia.
Keywords in Portuguese
Distorção harmônica
Medição
Qualidade de energia
Transdutor
Abstract in Portuguese
A Agência Nacional de Energia Elétrica (ANEEL) deverá estabelecer a regulamentação para distúrbios de qualidade de energia em um futuro próximo. Há ainda questões em aberto sobre os procedimentos de medição e limites máximos para os indicadores de qualidade de energia. Este trabalho aborda uma dessas questões, que é a conexão de transdutores e os impactos nos índices de qualidade de energia associados. Simulações em ATPDraw e campanhas de medição foram realizadas de modo a identificar o comportamento dos indicadores de distorção harmónica sob as duas configurações possíveis de conexão de transdutores: dois equipamentos com ligação entre fases ou três com ligação fase-neutro. Os resultados das simulações e os valores medidos mostram grandes discrepâncias entre ambas as configurações, e as diferenças tornam-se ainda mais significativas com o incremento do desequilíbrio do sistema elétrico. As causas subjacentes deste fenômeno são investigadas e discutidas
Title in English
The impact of transducers conection type in power quality measurements.
Keywords in English
Harmonic distortion
Measurement
Power quality
Transducer
Abstract in English
The Brazilian electricity regulatory agency (ANEEL) is expected to establish a legal framework for quality disturbances in the near future. There are still some open questions regarding metering procedures and maximum limits for Power Quality indicators. This work addresses one of such issues, namely the connection of the associated transducers and its impact on PQ indexes. Simulations in ATPDraw and on-field measurement campaigns were carried out so as to identify the behavior of harmonic distortion indicators under the two possible transducer configurations: two phase-to-phase or three phase-to-neutral transducers. Simulation results and measured values show large discrepancies between both configurations, and the differences become more significant as the electrical systems unbalance increases. The underlying causes of this phenomenon are investigated and discussed.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2013-07-19
 
WARNING: The material described below relates to works resulting from this thesis or dissertation. The contents of these works are the author's responsibility.
  • PIGNATTI, A. A., AHN, Se Un, e Schmidt, H.P. Impacto da conexão dos transdutores nas medições de Qualidade de Energia. In IX Conferência Brasileira Sobre Qualidade da Energia Elétrica, Cuiabá, 2011. IX Conferência Brasileira Sobre Qualidade da Energia Elétrica., 2011.