• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Disertación de Maestría
DOI
https://doi.org/10.11606/D.3.2016.tde-13062016-090911
Documento
Autor
Nombre completo
Omar Chayña Velásquez
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2015
Director
Tribunal
Senger, Eduardo Cesar (Presidente)
Manassero Junior, Giovanni
Reis Filho, Francisco Antonio
Título en portugués
Ajuste e ensaio de sistemas de proteção de geradores síncronos.
Palabras clave en portugués
Faltas internas
Geração de energia elétrica
Proteção de geradores síncronos
Proteção de sistemas elétricos
Proteção digital
Real time digital
Relé microprocessado.
Resumen en portugués
Os sistemas de proteção dos elementos da rede elétrica desempenham um papel de fundamental importância na segurança e confiabilidade dos sistemas de potência. A não atuação ou a atuação incorreta dos relés de proteção durante uma falta localizada em um componente da rede pode transformar-se em um evento sistêmico de grandes proporções (blecaute). Esses eventos trazem riscos e elevados prejuízos econômicos à sociedade. A proteção dos geradores síncronos, apesar do alto custo e complexidade deste tipo de equipamento, não recebe a mesma atenção na literatura que a dedicada à proteção de outros elementos da rede, como, por exemplo, a das linhas de transmissão. Isso decorre do menor número de geradores existentes na rede e também da ideia que as faltas neste tipo de equipamento são menos frequentes. Este trabalho aborda os principais aspectos envolvidos com o projeto de um sistema de proteção para geradores síncronos de grande porte. Incialmente, discutese os principais conceitos associados com os geradores, de interesse para a tarefa de proteção. Particular atenção é dedicada às formas de aterramento e aos critérios adotados para projeto do resistor de aterramento utilizado nesse equipamento. Em seguida, apresentam-se as principais funções de proteção aplicáveis aos geradores, particularmente aquelas voltadas para a detecção de faltas nos enrolamentos do estator. Discute-se também os critérios de ajustes dos parâmetros dessas funções. Descreve-se o uso de uma plataforma laboratorial, baseada em simulador de tempo real (RTDS), para ensaio e análise do sistema de proteção visando validar seu correto desempenho frente às possíveis condições operativas que podem ser encontradas em campo. Finalmente, utilizando os conceitos desenvolvidos ao longo do trabalho, desenvolve-se um estudo de caso, onde é realizado o projeto e implementação do sistema de proteção dos geradores de uma usina hidrelétrica hipotética. Para avaliar e analisar o desempenho do sistema de proteção dessa rede exemplo, parametrizou-se o IED G60 (GE) e realizou-se inúmeras simulações na plataforma de testes proposta.
Título en inglés
Regeneration of productive systems through dynamic reallocation of resources with functional flexibility.
Palabras clave en inglés
Digital relay
Electric power generation
Internal fault
Microprocessor relay
Power system protection
Real time digital simulator
Synchronous generator protection
Resumen en inglés
Protection systems play a critical role in the safety and reliability of electric power systems. The non-operation or wrong operation of protective relays during a fault in a network element can evolve to a systemic event in large scale (blackout). These events bring risks and high economic losses to society. Despite the high cost and complexity, the protection of synchronous generators has not received much attention in the literature devoted to protection of other network elements, such as transmission lines. This stems from the smaller number of generators in the network and also the idea that the faults in this type of equipment are less frequent. This research discusses the main aspects involved in the design of a protection system for large synchronous generators. Initially, it discusses the key concepts of interest to the generation protection. Particular attention is given to grounding techniques and the criteria adopted for the design of grounding resistors used in those equipment. Then the main protection functions applicable to generators are presented, particularly those related to fault detection in the stator windings. The criteria for setting the parameters of these functions are also discussed. After that, the use of a laboratory shelf, based on Real-Time Digital Simulator (RTDS) for testing and analysis of the protection system, is described in order to validate the correct performance in face of possible operating conditions in the field. Finally, a study case is developed using the concepts developed throughout the research. Then, the design and implementation of the protection system of generators of a hypothetical hydroelectric plant are carried out. To evaluate and analyze the performance of this example network protection system, parameterized up IED G60 (GE) and held numerous simulations in the proposed test platform.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2016-06-13
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.