Tese de Doutorado
DOI
https://doi.org/10.11606/T.3.2008.tde-09022009-181024
Documento
Autor
Nome completo
Marcos Rogério Cândido
E-mail
Unidade da USP
Área do Conhecimento
Data de Defesa
Imprenta
São Paulo, 2008
Orientador
Banca examinadora
Zanetta Júnior, Luiz Cera (Presidente)
Baccalá, Luiz Antonio
Coury, Denis Vinícius
Moreira, Fernando Augusto
Pereira, Carlos Eduardo de Morais
Título em português
Aplicação da transformada Wavelet na análise da qualidade de energia em fornos elétricos a arco.
Palavras-chave em português
Análise de ondaletas-wavelets (análise de séries temporais)
Energia (qualidade)
Forno elétrico
Resumo em português
Neste trabalho, desenvolveu-se um novo método para a detecção e classificação dos distúrbios que afetam a qualidade de energia elétrica em sistemas elétricos industriais na presença de fornos elétricos a arco. Durante o processo de fusão dos fornos elétricos a arco, ocorrem diversos eventos que afetam o sistema elétrico ao qual estão inseridos, tendo como características: forma de onda do sinal de corrente altamente desequilibradas e com grande distorção devido aos harmônicos, efeitos de cintilação; bem como afundamento e elevação nos sinais de tensão. O método ora proposto foi aplicado a sinais reais, permitindo a detecção e classificação dos distúrbios múltiplos na forma de onda do sinal de tensão, proveniente da operação dos fornos elétricos a arco. Para tal, foi usada como base do algoritmo, uma técnica baseada na Transformada Wavelet, aplicada aos sinais não-estacionários de uma instalação industrial com três fornos elétricos a arco.
Título em inglês
Application of wavelet transform for power quality analysis in electric arc furnace.
Palavras-chave em inglês
Electric arc furnace
Multiple disturbances
Power quality
Wavelet
Resumo em inglês
A new method for the detection and classification of the disturbances that affect the electric power quality in industrial electric systems with electric arc furnaces was developed in this work. During the fusion process of the electric arc furnaces, may occur several events that affect the electric system to which it is inserted may occur, having as characteristic: waveform of the signal of current highly unbalanced and with great distortion due to the harmonic, scintillation effects; as well as sag and swell in the voltage signals.The method proposed was applied to real signals, allowing the detection and classification of the multiple disturbances in the waveform of the voltage signal originating from the operation of the electric arc furnace. For this purpose, a technique based on Wavelet Transform will be used and applied to the not-stationary signals of an industrial installation with three electric arc furnaces.
 
AVISO - A consulta a este documento fica condicionada na aceitação das seguintes condições de uso:
Este trabalho é somente para uso privado de atividades de pesquisa e ensino. Não é autorizada sua reprodução para quaisquer fins lucrativos. Esta reserva de direitos abrange a todos os dados do documento bem como seu conteúdo. Na utilização ou citação de partes do documento é obrigatório mencionar nome da pessoa autora do trabalho.
Data de Publicação
2009-08-13
 
AVISO: Saiba o que são os trabalhos decorrentes clicando aqui.