Mémoire de Maîtrise
DOI
https://doi.org/10.11606/D.3.2017.tde-07112017-151817
Document
Auteur
Nom complet
André de Souza Melo
Adresse Mail
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Paulo, 2017
Directeur
Jury
Costa, Eduardo Coelho Marques da (Président)
Kurokawa, Sérgio
Liboni, Luisa Helena Bartocci
Titre en portugais
Identificação de pontos quentes em transformadores de potência por meio de técnicas não invasivas.
Mots-clés en portugais
Gases
Método dos elementos finitos
Transformadores e reatores
Resumé en portugais
Esta pesquisa apresenta uma metodologia, baseada em duas técnicas não invasivas para identificação e diagnóstico de pontos quentes em transformadores de potência durante plena operação ou em fase de projeto. A primeira técnica é baseada na medição de radiação infravermelha, emitida pelo equipamento em funcionamento e registrada por meio de análise termográfica. A segunda técnica é possível a partir do conhecimento prévio das características construtivas do transformador, fazendo uso do Método dos Elementos Finitos (MEF). A segunda técnica pode ser validada a partir das medições realizadas utilizando a primeira técnica. A formação de gases no interior dos transformadores de potência, devido à elevação da temperatura do óleo isolante em função dos pontos quentes, é discutida em detalhes com base nas normas técnicas estabelecidas pelo IEEE e IEC. As técnicas e procedimentos abordados ao longo dessa pesquisa foram obtidos a partir de um transformador com potência nominal de 120 MVA e relação de tensão 13,8/230 kV, projetado para integrar uma fazenda eólica ao Sistema Interligado Nacional (SIN).
Titre en anglais
Identification of hot spots in power transformers using non-invasive techniques.
Mots-clés en anglais
DGA
Finite Elements Method
Hot spots
Insulating oil
Insulation coordination
Power transformer
Resumé en anglais
This research presents a methodology based on two noninvasive techniques for identification and diagnostic of hot spots in power transformers during operation or project development. The first is based on measurements of infrared radiation from the equipment during operation and recording by thermography. The second technique is possible from the previous knowing of the constructive characteristics of the power transformer, by using the Finite Element Method (FEM). The second technique can be validated from measurements obtained using the first technique. The gas formation into the power transformers, because of the high temperatures in the insulating oil due to the hot spots, is discussed in details based on normative recommendations well established by the IEEE and IEC. All techniques and procedures to be approached in this research were obtained using a 120-MVA power transformer with voltage relationship of 13.8/230 kV that was projected to interconnect a wind farm to the Interconnected Brazilian System (Sistema Interligado Nacional - SIN).
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Date de Publication
2017-11-09
 
AVERTISSEMENT: Apprenez ce que sont des œvres dérivées cliquant ici.
Tous droits de la thèse/dissertation appartiennent aux auteurs
CeTI-SC/STI
Bibliothèque Numérique de Thèses et Mémoires de l'USP. Copyright © 2001-2024. Tous droits réservés.