Titre en portugais
Sistema digital para manobra sincronizada de disjuntores - estudo e especificação funcional.
Mots-clés en portugais
chaveamento controlado
disjuntores
manobra sincronizada
sobrecorrente
sobretensão
Resumé en portugais
Nesta dissertação, discorre-se sobre manobra sincronizada de disjuntores. Entre as atividades desenvolvidas para a sua elaboração estão a análise de transitórios causados por manobras em capacitores, reatores e linhas de transmissão, estudos de sobretensão e estudos para a determinação de instantes favoráveis às manobras, sob o ponto de vista de diminuição de sobretensões. Completa a dissertação a especificação de equipamento de sincronismo que, a partir de medições em tempo real de variáveis elétricas - que interferem nas sobretensões - e de variáveis climáticas - que interferem no tempo de acionamento dos contatos dos disjuntores - calculam o tempo de atraso necessário para o fechamento elétrico em instantes mais convenientes.
Titre en anglais
Digital system for synchronized switching of circuit breakers.
Mots-clés en anglais
circuit breakers
controlled switching
overcurrent
overvoltage
synchronized maneuver
Resumé en anglais
The scope of this dissertation is the study of synchronized switching of circuit breakers. The transients caused by capacitor, reactor and transmission line switching are analyzed, for overvoltage evaluation and to determined the favorable time in the wave that leads to smallest overvoltages. Finally the specification of an equipment is produced. The equipment acquire, in real time, the values of electrical variables (current and voltages) the ambient temperature and oil pressure in the circuit breaker operating mechanism, voltage in the auxiliary system and assign a delay in the breaker switching time in order to control overvoltages.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Date de Publication
2006-09-13
 
AVERTISSEMENT: Apprenez ce que sont des œvres dérivées cliquant ici.
Tous droits de la thèse/dissertation appartiennent aux auteurs
CeTI-SC/STI
Bibliothèque Numérique de Thèses et Mémoires de l'USP. Copyright © 2001-2024. Tous droits réservés.