Master's Dissertation
DOI
https://doi.org/10.11606/D.3.2006.tde-05092006-133417
Document
Author
Full name
Marcus Vinicius Garbelotti
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2006
Supervisor
Committee
Jardini, Jose Antonio (President)
Magrini, Luiz Carlos
Tahan, Carlos Marcio Vieira
Title in Portuguese
Sistema digital para manobra sincronizada de disjuntores - estudo e especificação funcional.
Keywords in Portuguese
chaveamento controlado
disjuntores
manobra sincronizada
sobrecorrente
sobretensão
Abstract in Portuguese
Nesta dissertação, discorre-se sobre manobra sincronizada de disjuntores. Entre as atividades desenvolvidas para a sua elaboração estão a análise de transitórios causados por manobras em capacitores, reatores e linhas de transmissão, estudos de sobretensão e estudos para a determinação de instantes favoráveis às manobras, sob o ponto de vista de diminuição de sobretensões. Completa a dissertação a especificação de equipamento de sincronismo que, a partir de medições em tempo real de variáveis elétricas - que interferem nas sobretensões - e de variáveis climáticas - que interferem no tempo de acionamento dos contatos dos disjuntores - calculam o tempo de atraso necessário para o fechamento elétrico em instantes mais convenientes.
Title in English
Digital system for synchronized switching of circuit breakers.
Keywords in English
circuit breakers
controlled switching
overcurrent
overvoltage
synchronized maneuver
Abstract in English
The scope of this dissertation is the study of synchronized switching of circuit breakers. The transients caused by capacitor, reactor and transmission line switching are analyzed, for overvoltage evaluation and to determined the favorable time in the wave that leads to smallest overvoltages. Finally the specification of an equipment is produced. The equipment acquire, in real time, the values of electrical variables (current and voltages) the ambient temperature and oil pressure in the circuit breaker operating mechanism, voltage in the auxiliary system and assign a delay in the breaker switching time in order to control overvoltages.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2006-09-13
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.