Master's Dissertation
DOI
https://doi.org/10.11606/D.3.2013.tde-11072014-104109
Document
Author
Full name
Bruno Castro Silva
E-mail
Institute/School/College
Knowledge Area
Date of Defense
Published
São Paulo, 2013
Supervisor
Committee
Garcia, Claudio (President)
Perez, José Manuel Gonzalez Tubio
Romano, Rodrigo Alvite
Title in Portuguese
Avaliação da eficiência de compensadores de atrito aplicados a válvulas de controle.
Keywords in Portuguese
Compensação de atrito
CR
Knocker
Quantificação de atrito
Two-move
Válvulas de controle
Abstract in Portuguese
O objetivo deste trabalho é reduzir o efeito do atrito estático em malhas de controle. A não-linearidade inserida por esse fenômeno pode diminuir a eficiência de um controlador PID e até tornar o sistema em malha fechada oscilatório. Para minimizar esse problema, são testados compensadores presentes na literatura e que não necessitam de modelos internos, os quais, em princípio, podem ser implementados em CLPs e SDCDs com facilidade. Apesar dos compensadores não utilizarem um modelo da válvula em seu algoritmo, é necessário conhecer a magnitude do atrito para parametrizá-los. Por este motivo, os primeiros tópicos desta dissertação são sobre modelos de atrito e técnicas para estimar seus parâmetros. Após estes tópicos, são introduzidos os compensadores de atrito. Alguns dos métodos avaliados foram modificados para tentar aprimorar os resultados. Apesar da teoria poder ser aplicada para uma grande diversidade de processos, os algoritmos foram aplicados a uma malha de controle de vazão de água utilizando válvulas de controle. O objetivo assumido é minimizar o ITAE (Integral Time Absolute Error) e o desgaste gerado nos equipamentos, devido à movimentação excessiva da haste da válvula. Também se verifica o tempo de subida do sistema em malha fechada. Além de testar os compensadores em uma malha de controle de vazão, também foram realizados testes com os compensadores em uma malha de controle de posição, que por sua vez recebe o set-point de uma malha de controle de vazão (controle em cascata). Os resultados mostram que, utilizando os compensadores, é possível que uma válvula com alto índice de atrito apresente um desempenho próximo ao de uma válvula com baixo índice de atrito sem compensação, ou seja, foi possível compensar o atrito na haste.
Title in English
Avaluation of the efficiency of friction compensators applied to control valves.
Keywords in English
Control valves
CR
Friction compensation
Friction quantification
Knocker
Twomove
Abstract in English
The aim of this work is to reduce the effect of the static friction in control loops. The non-linearity inserted by this phenomenon may decrease the efficiency of a PID controller and even make the closed loop system oscillatory. To minimize this problem some compensation methods present in the literature that do not require internal models were tested, which, theoretically, can be easily implemented in a PLC or DCS. Even thought the compensation methods do not require internal models, it is necessary to know the friction magnitude in order to set their parameters. With that in mind, the first topics of this dissertation friction models and how to identify their parameters. After these topics the friction compensation methods are introduced. Some of these methods where modified, with the purpose of improving the results. Although the theory may be applied to a great variety of process, these algorithms were applied to a water flow control loop using control valves. The assumed objective is to minimize the ITAE (Integral Time Absolut Error) and the wearing of the equipments due to excessive movement of the valve stem. The rising time of the closed loop system is also verified. Besides testing these compensation methods in a flow control loop, they were also tested in a position control loop, that receives its set-point from a flow control loop (cascade control).
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Publishing Date
2014-07-18
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI