Disertación de Maestría
DOI
https://doi.org/10.11606/D.18.2012.tde-26042012-100422
Documento
Autor
Nombre completo
Geraldo Lupi Filho
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2012
Director
Tribunal
Altafim, Ruy Alberto Corrêa (Presidente)
Ahn, Se Un
Silva, Ivan Nunes da
Título en portugués
Comparação entre os critérios de diagnósticos por análise cromatográfica de gases dissolvidos em óleo isolante de transformador de potência
Palabras clave en portugués
Análise de gases dissolvidos
Cromatografia gasosa
Método de detecção de falhas
Transformador de potência
Resumen en portugués
Existem inúmeras ferramentas e metodologias para o diagnóstico de falhas em transformadores de potência, tanto para a monitoração e acompanhamento do equipamento em operação (planta fixa) como àquele retirado e abrigado em laboratórios de unidades fabris. Em função dos custos envolvidos no transporte dos equipamentos, manuseio para a substituição, energia não faturada nos períodos de manobras e custos adicionais dos ensaios para voltar com o equipamento em operação, as principais metodologias que se destacam são aquelas direcionadas ao equipamento em operação e também as escolhidas para serem analisadas neste trabalho. Após um estudo sistemático dessas metodologias, tais como termográfica, emissão acústica e análise dos gases dissolvidos no óleo, denominada cromatografia, verificou-se que esta última se destaca como a mais econômica e a mais difundida na identificação das falhas. Contudo, na cromatografia, existem diferentes critérios de análise baseados nas relações e quantidades de diferentes tipos de gases e que são usados pelas companhias concessionárias de forma indiscriminada, gerando muitas dúvidas quanto à sua validade. Esta pesquisa teve como principal foco a comparação desses critérios usando como base de dados àqueles fornecidos pela IEC e pela Companhia Paulista de Força e Luz (CPFL). A base de dados da CPFL contem aproximadamente quatro mil ensaios cromatográficos, colhidas nas ultimas três décadas correspondendo a 500 unidades transformadoras, nas potências de 5,0 a 50 MVA, instaladas em subestações nas tensões primárias de 69 e 138 kV, e secundária de 13,8 kV. Também fez parte dessa pesquisa a definição de um conjunto de critérios que melhor identificam as falhas em transformadores.
Título en inglés
Comparison between the diagnostic criteria for chromatographic analysis of gases dissolved in insulating oil for transformer
Palabras clave en inglés
Dissolved gas analysis
Gas chromatography
Method of fault detection
Power transformer
Resumen en inglés
There are numerous tools and methodologies for fault diagnosis in power transformers, either for monitoring and tracking equipment in operation (fixed plant) or for those removed and housed in laboratories plants. Due to the costs involved in transporting the equipment, handling for the replacement, unbilled energy during periods of maneuvers and additional costs of the tests to return with the equipment in operation, the main methodologies that stand out are those using the equipment in operation and also those chosen to be analyzed in this work. After a systematic study of these methods such as thermography, and acoustic emission and analysis of gases dissolved in the oil, known as chromatography, it was found that the latter stands out as the most economical and most widely in the identification of faults. However, in chromatography, there are different criteria based on the relationships of different types and quantities of gases that are used by electrical companies indiscriminately, raising many questions about its validity. This research was mainly focused on the comparison of these criteria using the database as those provided by IEC and the Companhia Paulista de Força e Luz (CPFL). The database of CPFL contains approximately four thousand chromatographic assays from the last three decades, corresponding 500 transforming units, from 5 to 50 MVA, in substations with primary voltages of 138 kV and 69 and secondary of 13,8 kV. Was also studied the definition of a set of criteria which identify faults in transformers.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Geraldo.pdf (7.13 Mbytes)
Fecha de Publicación
2012-05-04
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.