Mémoire de Maîtrise
DOI
https://doi.org/10.11606/D.18.2015.tde-25052015-114845
Document
Auteur
Nom complet
Robson Roberto Sguaçabia
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Carlos, 2015
Directeur
Jury
Vieira Júnior, José Carlos de Melo (Président)
Oleskovicz, Mário
Salles, Newton José de
Titre en portugais
Avaliação do impacto da geração distribuída sobre o sistema de proteção de sobrecorrente de uma rede de distribuição operando em ilhamento intencional
Mots-clés en portugais
Geração distribuída
Ilhamento intencional
Proteção de redes de distribuição
Resumé en portugais
O crescente número de geradores distribuídos conectados em redes de distribuição de energia elétrica é uma realidade dos sistemas elétricos de todo o mundo. Embora a política atual seja desconectar os geradores distribuídos do sistema elétrico de potência (SEP) caso ocorra uma falha na rede da concessionária, conforme preconizam os principais guias técnicos nacionais e internacionais, o módulo 3 dos Procedimentos de Distribuição de Energia Elétrica no Sistema Elétrico Nacional (PRODIST) mostra-se favorável à operação ilhada, pois afirma que este tipo de operação pode ser realizado em comum acordo entre as centrais geradoras de energia e o Operador Nacional do Sistema Elétrico (ONS), permitindo alcançar uma maior disponibilidade no fornecimento de energia. No entanto, para que a operação ilhada seja possível e possa ser praticada de forma segura, o ilhamento intencional precisa superar alguns desafios, dentre os quais estão aqueles relacionados ao sistema de proteção da rede de distribuição, tais como: coordenação indevida de dispositivos de proteção, perda da sensibilidade da proteção, abertura inadequada de fusíveis e religamentos automáticos fora de sincronismo. Portanto, este trabalho avalia o impacto da geração distribuída (GD) sobre o sistema de proteção de sobrecorrente de uma rede de distribuição operando ilhada. A ideia principal é dividir a rede em regiões delimitadas pelos dispositivos de proteção existentes, para em seguida, adequá-los à nova situação operacional, certificando se os ajustes propostos atendem ao comportamento síncrono e estável do sistema de geração por meio de uma análise de estabilidade transitória. Propõe-se então um conjunto de procedimentos para tomada de ações que permitam readequar o sistema de proteção de sobrecorrente existente à operação ilhada. Os resultados obtidos demonstram que a inibição do religamento automático e da curva de atuação instantânea acrescida de reajustes nas curvas temporizadas dos relés e religadores, melhoraram a coordenação e seletividade da rede operando ilhada.
Titre en anglais
Impact assessment of the distributed generation on the overcurrent protection system of a distribution network operating in intentional islanding
Mots-clés en anglais
Distributed generation
Intentional islanding
Protection of distribution system networks
Resumé en anglais
The growing number of distributed generators connected to electricity distribution networks is a reality of electrical systems throughout the world. Although the current policy is to disconnect the distributed generators from the electric power system (EPS) in the event of loss of mains, as required by main national and international technical guides, the module 3 of the Procedures for Electric Power Distribution in the Electric National System (PRODIST) shows itself in favor of islanded operation, it states that this type of operation can be carried out in agreement between power generation plants and the National Electric System Operator (ONS), allowing achieve larger availability in energy supply. However, to make the islanded operation possible and safe, the intentional islanding must overcome some challenges, among which are those related to the protection system of the distribution network, such as improper coordination of protective devices, loss of protection sensitivity, inadequate opening of fuses and automatic reclosing out of synchronism. Therefore, this work evaluates the impact of distributed generation (DG) on the overcurrent protection system of a distribution network operating islanded. The main idea is to divide the network into regions bounded by existing protection devices, to then adapt them to the new operational situation, making sure that the proposed adjustments meet the synchronous and stable behavior of the generation system by means of a transient stability analysis. Thus, a set of procedures is proposed to indicate actions that allow readjusting the existing overcurrent protection system to the islanded operation. The results demonstrate that the inhibition of automatic restart and of the instantaneous operating curve plus adjustments in time delay curves of relays and reclosers, improved the coordination and selectivity of the network operating islanded.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Robson.pdf (3.39 Mbytes)
Date de Publication
2015-06-01
 
AVERTISSEMENT: Le matériau se réfère à des documents provenant de cette thèse ou mémoire. Le contenu de ces documents est la responsabilité de l'auteur de la thèse ou mémoire.
  • LIMA, R. L., SGUACABIA, R. R., e Vieira, Jose C. M. Análise dos Requisitos Técnicos de Controle e de Qualidade da Energia Elétrica para Viabilizar a Operação Ilhada de Geradores Síncronos Distribuídos. In 10th International Conference on Industry Applications - INDUSCON 2012, Fortaleza, 2012. Anais., 2012.
Tous droits de la thèse/dissertation appartiennent aux auteurs
CeTI-SC/STI
Bibliothèque Numérique de Thèses et Mémoires de l'USP. Copyright © 2001-2024. Tous droits réservés.