Mémoire de Maîtrise
DOI
https://doi.org/10.11606/D.18.2014.tde-14102014-092706
Document
Auteur
Nom complet
Rodrigo Zempulski Fanucchi
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Carlos, 2014
Directeur
Jury
Oleskovicz, Mário (Président)
Barbosa, Daniel
Jorge, David Calhau
Titre en portugais
A detecção e a localização de faltas de alta impedância em sistemas de distribuição utilizando transformadas wavelets e redes neurais artificiais
Mots-clés en portugais
Detecção e localização de faltas
Faltas de alta impedância
Sistemas de proteção
Sistemas elétricos de distribuição
Técnicas inteligentes
Resumé en portugais
A ocorrência de faltas em sistemas elétricos de distribuição de energia é algo indesejável, porém, inerente ao mesmo devido a sua topologia normalmente aérea. Entre essas faltas, destacam-se as de alta impedância devido às características de corrente de baixa magnitude que surgem quando de sua ocorrência. No presente trabalho, um método baseado em três módulos é apresentado para a detecção e localização de faltas de alta impedância (FAI). No Módulo 1, é realizado um monitoramento contínuo dos sinais de corrente de forma a detectar a ocorrência de uma descontinuidade que pode estar vinculada a ocorrência de uma FAI. Caso haja essa detecção, o Módulo 2 é ativado de forma a analisar se o evento é realmente uma FAI. Por último, depois de detectada a FAI, o Módulo 3 é inicializado e a localização da falta, estimada. Para possibilitar a análise do método proposto e validar os resultados obtidos, um sistema de distribuição real, em conjunto com todas as etapas do sistema de aquisição de dados, foi modelado no software ATP/EMTP. Essa modelagem foi validada a partir de dados reais obtidos quando da ocorrência em campo de um curto-circuito bifásico. Vale ressaltar que um estudo de caso referente à importância da detecção e localização de um evento relacionado a uma FAI em uma concessionária de energia foi também analisado no início do trabalho de forma a mostrar o possível impacto da localização de FAIs nos indicadores de qualidade de serviço na mesma. Pelos resultados observados, a abordagem como um todo se mostra promissora e passível de aplicação no sistema real simulado e avaliado.
Titre en anglais
Detection and location of high impedance faults in distribution systems using wavelets transforms and artificial neural networks
Mots-clés en anglais
Electrical distribution systems
Fault location
High impedance faults
Protection systems
Resumé en anglais
The occurrence of faults in overhead distribution networks is undesirable but common based on its topology. Among these events, High Impedance Faults (HIF) is one of the most important due to the fact that it has a small magnitude current. In this dissertation, a modular three-phase method is presented to enable HIF´s detection and location in a distribution system. In the Module 1, the phase currents are monitored in order to detect a discontinuity that can be associated with a HIF´s occurrence. If the Module 1 detected a discontinuity, the Module 2 is initiated and it analyses if the event can be classified as a HIF. Finally, if the Module 2 returns the event as a HIF, the Module 3 is initiated and the possible location of the HIF is estimated. To enable analysis of the proposed method and to validate the results, a real-based distribution system and the acquisition system of a digital relay were modeled in ATP/EMTP software. In order to validate the model, a simulated twophase fault were compared with the data obtained in a real event occurred in the analyzed distribution system. In order to present the importance of detecting and locating a HIF to a distribution utility, a case study was developed in the beginning of its work. Its importance is based on the improvement of the service quality indicators. Based on the results, the proposed method seems to be promising and applicable in a real distribution system.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.