Master's Dissertation
DOI
https://doi.org/10.11606/D.18.2015.tde-07042015-111816
Document
Author
Full name
Alexandre Vinicius Festa
Institute/School/College
Knowledge Area
Date of Defense
Published
São Carlos, 2015
Supervisor
Committee
Oleskovicz, Mário (President)
Arioli, Fernanda Caseño Trindade
Silva, Murilo da
Title in Portuguese
Diagnóstico de curtos-circuitos a partir da alocação otimizada de medidores em um sistema de distribuição subterrâneo
Keywords in Portuguese
Alocação otimizada de medidores
Classificação e localização de faltas
Monitoramento
Qualidade da energia elétrica
Redes neurais artificiais
Sistemas de distribuição subterrâneos
Abstract in Portuguese
O monitoramento e diagnóstico, com a consequente localização dos curtos-circuitos em Sistemas de Distribuição (SD), fazem parte de um processo complexo, exigindo esforços e agilidade das equipes técnicas de manutenção das concessionárias de energia elétrica. Quando se trata de um SD Subterrâneo (SDS), a complexidade de localização das faltas aumenta, pois não é possível realizar a inspeção visual. Por este motivo, desenvolver e aprimorar métodos para monitorar, classificar e localizar as situações de faltas em SD tem sido de relevante interesse para a comunidade técnico-científica nos últimos anos. Neste contexto, apresenta-se nesta pesquisa um método para processar as informações necessárias para classificar e localizar a ocorrência de um curto-circuito (monofásico, bifásico e/ou trifásico, com e/ou sem o envolvimento da terra) em um SDS. O processamento das informações foi realizado por meio da observação da propagação dos afundamentos de tensão, decorrentes de curtos-circuitos passíveis de ocorrência no SDS, e pela alocação de um número reduzido de medidores, permitindo a classificação e localização precisa da falta. Um dos diferenciais da metodologia proposta é que esta utiliza somente os valores eficazes das tensões trifásicas, registradas em medidores estrategicamente alocados, para indicação da área afetada e classificação das fases envolvidas. A metodologia é baseada no emprego de redes neurais artificiais. Os resultados encontrados são promissores, indicando a aplicabilidade da metodologia proposta.
Title in English
Diagnostic short-circuits from the optimized allocation meters in a underground distribution system
Keywords in English
Artificial neural networks
Classification and fault location
Monitoring
Optimized allocation meters
Power quality
Underground distribution systems
Abstract in English
The monitoring and diagnostics, with the consequent localization of short circuits in Distribution Systems (DS), are part of a complex process, requiring efforts and agility of the technical teams of maintenance of electric utilities. In the case of an underground DS (UDS), the location of faults complexity increases, because it is not possible to perform visual inspection. For this reason, develop and improve methods to monitor, sort and locate the fault situations in DS has been of relevant interest to the technical-scientific community in recent years. In this context, this study presents a method for processing the information required to classify and locate the occurrence of a short circuit (single phase, biphasic and / or phase with and / or without the involvement of the earth) on a UDS. The information processing was carried out by observing the propagation of voltage sags, caused by short circuits that may occur in the UDS, and the allocation of a few meters, allowing classification and precise location of the fault. One of the proposed methodology differentials is that it uses only the RMS values of the three-phase voltages, registered in strategically located meters, for indicating the affected area and classification of the phases involved. The methodology is based on the use of artificial neural networks. The results found are promising, indicating the applicability of the proposed methodology.
 
WARNING - Viewing this document is conditioned on your acceptance of the following terms of use:
This document is only for private use for research and teaching activities. Reproduction for commercial use is forbidden. This rights cover the whole data about this document as well as its contents. Any uses or copies of this document in whole or in part must include the author's name.
Alexandre.pdf (5.59 Mbytes)
Publishing Date
2015-04-15
 
WARNING: Learn what derived works are clicking here.
All rights of the thesis/dissertation are from the authors
CeTI-SC/STI
Digital Library of Theses and Dissertations of USP. Copyright © 2001-2024. All rights reserved.