Disertación de Maestría
DOI
https://doi.org/10.11606/D.18.2016.tde-04102016-100143
Documento
Autor
Nombre completo
Thiago Reginato Lunardi
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2016
Director
Tribunal
Vieira Júnior, José Carlos de Melo (Presidente)
Arioli, Fernanda Caseño Trindade
Fernandes, Ricardo Augusto Souza
Título en portugués
Detecção de ilhamento em sistemas de distribuição com múltiplos geradores distribuídos utilizando redes neurais artificiais
Palabras clave en portugués
Detecção de ilhamento
Geração distribuída
Gerador de indução duplo alimentado
Gerador síncrono
Redes neurais artificiais
Resumen en portugués
A inserção de geradores distribuídos nas redes de distribuição de energia elétrica está aumentando consideravelmente devido à possibilidade de maior proximidade destes geradores com os mercados consumidores, fatores ambientais, aprimoramentos das tecnologias atuais de geração de energia elétrica e desenvolvimentos de outras novas, alterações de legislações e incentivos governamentais. Este novo cenário traz também a necessidade de maior atenção devido à possibilidade de ocorrência de ilhamentos não intencionais. Nestas situações, o gerador distribuído deve ser desconectado imediatamente após a detecção do evento. Métodos tradicionais, como relés de tensão e de frequência, mostram bom desempenho quando há um elevado desbalanço entre as potências geradas e as potências das cargas ilhadas. Nos casos de pequenos desbalanços de potência, o ilhamento pode não ser detectado por esses métodos. Neste contexto, este trabalho visa desenvolver um sistema de detecção de ilhamentos em sistemas de distribuição por meio da utilização de uma rede neural artificial do tipo Perceptron multicamadas. Utilizando-se uma rede neural devidamente treinada para o sistema elétrico estudado, obteve-se um bom desempenho na detecção de ilhamento, obtendo-se elevadas taxas de acerto. Além disso, o método proposto foi capaz de diferenciar corretamente situações normais de operação do sistema, tais como chaveamento de blocos de cargas, das situações de ilhamento. Os mesmos cenários foram testados utilizando as proteções convencionais de tensão, frequência e de taxa de variação de frequência, a fim de obter a comparação com o método proposto. Como resultado, o método baseado na rede neural apresentou desempenho superior aos demais sistemas de proteção, detectando o ilhamento dentro da faixa de 2 segundos em todos os casos simulados neste trabalho.
Título en inglés
Islanding detection in distribution systems with multiple distributed generators using artificial neural networks
Palabras clave en inglés
Distributed generation
Doubly-fed induction generator
Islanding detection
Synchronous generator
Resumen en inglés
The penetration of distributed generators into the power distribution systems has been increasing significantly due to the possibility of generating power next to the consumers, environmental issues, improvement and development of the generation technologies, regulatory changes and governmental incentives. This new scenario requires special attention to the possibility of unintentional islanding. In this situation, the distributed generator must be disconnected immediately after an islanding occurrence. Traditional anti-islanding protection schemes, such as voltage and frequency-based relays, are effective to detect islanding if there is a big power imbalance between generation and load inside the island. On the other hand, they may fail if the power imbalance is small. In this context, this work presents a new islanding detection method based on a Perceptron Multi-layer neural network. By using a neural network properly trained for the distribution system under study, the method has presented good performance with high islanding detection successful rates. Moreover, the proposed method was capable of distinguish the islanding occurrence from normal transient operating conditions, such as load switching. The same operating scenarios were used to test voltage, frequency and rate of change of frequency protection in order to perform a comparison with the proposed method. As result, the method presented superior performance detecting the islanding faster than 2 seconds in all the cases simulated in this work.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Thiago.pdf (2.15 Mbytes)
Fecha de Publicación
2016-10-06
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.