• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Tesis Doctoral
DOI
https://doi.org/10.11606/T.18.2015.tde-07042015-111551
Documento
Autor
Nombre completo
Rodrigo Augusto Modesto
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2015
Director
Tribunal
Silva, Sérgio Augusto Oliveira da (Presidente)
Batschauer, Alessandro Luiz
Cavalcanti, Marcelo Cabral
Mezaroba, Marcello
Monteiro, José Roberto Boffino de Almeida
Título en portugués
Estudo, projeto e implementação de sistemas UPQC/UPS trifásicos aplicados no condicionamento ativo de energia elétrica
Palabras clave en portugués
Condicionamento ativo de potência
Conversores PWM
Supressão de harmônicos
UPQC
UPS
Resumen en portugués
Este trabalho apresenta o estudo, análise e a implementação de três topologias de condicionadores ativos de energia elétrica, utilizados para a melhoria da qualidade da energia em sistemas elétricos trifásicos a quatro fios. Estes condicionadores de qualidade de energia podem trabalhar tanto como um condicionador unificado de qualidade de energia (UPQC), bem como uma fonte de alimentação ininterrupta (UPS), permitindo: (i) a supressão das correntes harmônicas da carga; (ii) a compensação de energia reativa da carga; (iii) compensação dos desequilíbrios das correntes de carga; (iv) a compensação de desequilíbrios de tensão da rede; (v) supressão das tensões harmônicas da rede elétrica; (vi) a regulação das tensões de saída (tensões de carga); e (vii) fornecimento de energia ininterrupta para as cargas críticas (sistema UPS). Dentre as três topologias de UPQC/UPS estudadas, uma delas é proposta neste trabalho com o intuito de reduzir a tensão no barramento CC. Além disso, todas as topologias em estudo são constituídas por dois conversores PWM, nos quais é adotada uma estratégia de controle dual. Desse modo, o conversor colocado em paralelo com a carga, funciona como uma fonte de tensão senoidal, enquanto que o conversor colocado em série entre a rede elétrica e a carga, é controlado para operar como uma fonte de corrente senoidal. Tanto os controladores de tensão, quanto os de corrente são implementados no referencial síncrono dq0. Além disso, a técnica de modulação vetorial espacial tridimensional (3-D-SVM) é empregada nos conversores. Testes experimentais são apresentados para validar o desenvolvimento teórico e verificar o bom desempenho estático e dinâmico dos condicionadores ativos de energia elétrica, operando como UPQC, bem como sistema UPS.
Título en inglés
Study, design and implementation of an UPQC/UPS systems applied in three-phase active power conditioning
Palabras clave en inglés
Active power conditioning
Harmonics suppression
PWM converters
UPQC
UPS
Resumen en inglés
This work presents the study, analysis and implementation of three topologies of active power conditioners, which are used to improve the power quality in three-phase four-wire systems. These power quality conditioner can work as unified power quality conditioner (UPQC), as well as an uninterruptible power supply (UPS) system allowing: (i) suppression of load harmonic currents; (ii) compensation of load reactive power; (iii) load unbalances compensation; (iv) utility voltage unbalances compensation; (v) utility voltage harmonics suppression; (vi) regulation of the output voltages (load voltages); and (vii) uninterruptible power for critical loads when working as UPS system. Among the three topologies of UPQC/UPS studied, one of them is proposed in this work in order to reduce the DC-bus voltage. Besides, all the topologies are comprised of two PWM converters, where a dual control strategy is adopted. The first converter, which is placed in parallel with the load, operates as a sinusoidal voltage source, while the second, which is placed in series between the utility grid and the load, is controlled to operate as a sinusoidal current source. Both the voltage and current controllers are implemented into the synchronous rotating reference frame (dq0-axes). In addition, the series and parallel converters use the three-dimensional space vector modulation (3-D-SVM) technique. The experimental tests are presented to validate the theoretical development and to verify the effective static and dynamic performance of the proposed active power conditioners, operating as UPQC and UPS.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Rodrigo.pdf (5.52 Mbytes)
Fecha de Publicación
2015-04-14
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.