Mémoire de Maîtrise
DOI
https://doi.org/10.11606/D.18.2011.tde-15072011-093629
Document
Auteur
Nom complet
Eloá Cristina Figueirinha Pelegrino
Adresse Mail
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Carlos, 2011
Directeur
Jury
Reali, Marco Antonio Penalva (Président)
Damianovic, Márcia Helena Rissato Zamariolli
Vidal, Carlos Magno de Sousa
Titre en portugais
Emprego de coagulante à base de tanino em sistema de pós-tratamento de efluente de reator UASB por flotação
Mots-clés en portugais
Coagulante à base de tanino
Flotação
Polímero
Pós-tratamento de efluente de reator UASB por flotação
Tratamento de esgoto sanitário
Resumé en portugais
O presente trabalho teve como objetivo principal a avaliação da eficiência de remoção de carga orgânica, fósforo e sólidos em suspensão de sistema de flotação tratando esgoto sanitário pré-tratado em reatores UASB, da ETE Monjolinho da cidade de São Carlos/SP, e coagulado com tanino associado ou não a polímeros sintéticos. Os ensaios com variação de dosagem de coagulante Tanino e polímeros (polímero catiônico, polímero não-iônico e polímero aniônico) foram realizados em escala de laboratório, com o uso do equipamento flotateste. Em todos os ensaios foram fixados os valores de gradiente de velocidade na mistura rápida (800/s) e na floculação (90/s), ao tempos de detenção na mistura rápida (20 s) e na floculação (15 min) e, a pressão de saturação 5 Bar e a razão de recirculação (17%). Durante os ensaios com unidade de flotação em escala de bancada foram avaliados três valores de velocidades de flotação: 12,0 cm/min, 16,0 cm/min e 20,0 cm/min. Os ensaios foram divididos em duas fases: a fase 1 teve como objetivo analisar a resposta do sistema de flotação com o emprego do coagulante Tanino no tratamento do efluente do reator UASB da ETE Monjolinho (fase 1A) e também determinar as duas dosagens do coagulante Tanino mais adequadas para o tratamento do efluente de UASB da ETE Monjolinho para cada polímero testado (fase 1B). As fases 1A e 1B foram realizadas com efluente coletado às 8:00 h e 14:00 h, respectivamente. A fase 2 teve como objetivo a busca da dosagem ótima de tanino dentro de uma faixa mais estreita de valores, assim como a verificação do melhor tipo e dosagem de polímero sintético (não-iônico, aniônico e catiônico) para ser associado ao coagulante tanino. Na fase 1A, verificou-se que a flotação foi efetiva para remoção de cor aparente mesmo para dosagem nula de coagulante Tanino. Quanto à turbidez, verificou-se efeito marcante da adição de dosagem crescente de coagulante no aumento da eficiência de remoção desse parâmetro. Após a obtenção dos resultados da fase 1B, foram escolhidas para a fase 2 as duas menores dosagens de coagulante capazes de promover redução da turbidez em pelo menos 85%. Além destas duas dosagens, foram avaliados na fase 2 outras 3 dosagens compreendidas entre elas. Sendo assim, na fase 2 foram estudadas as doses de 65, 75, 85, 95 e 105 mg/L de coagulante, cada qual associada a seis dosagens de cada um dos polímeros estudados. Entre os tratamentos empregados, pôde-se verificar maior eficácia do polímero não-iônico e do polímero catiônico para o tratamento por flotação, associado ao coagulante tanino. O conjunto de dosagem de coagulante tanino e polímero mais vantajoso, ou seja, menor dosagem de tanino que, associada a polímero, apresentou remoção satisfatória dos parâmetros estudados, foi 65 mg/L de Tanino e 2,0 mg/L de polímero catiônico, atingindo remoções de 95,2% de turbidez (Residual de 3,65 NTU), 82,1% de cor aparente (Residual de 98 mgPT/L), 49,2% de fósforo total (Residual de 3,2 mg/L), 80,7% de DQO (Residual de 25 mg/L) e 87,9 % de SST (Residual de 13 mg/L) nas condições encontradas na época dos ensaios, para o pós-tratamento por flotação de efluente de reator UASB da ETE Monjolinho, São Carlos/SP.
Titre en anglais
Use of tannin-based coagulant in exhaust post-treatment of UASB reactor effluent by flotation
Mots-clés en anglais
Flotation
Polymer
Post treatment of UASB reactor effluent by flotation
Tannin-based coagulant
Wastewater treatment
Resumé en anglais
The main objective of this work is the evaluation of the efficiency of removal of organic load, phosphorus and suspended solids in the flotation system treating domestic wastewater pretreated in UASB reactors, of the Monjolinho Wastewater Treatment Plant (WWTP) of Sao Carlos, SP and clotted with tannin alone or combined with synthetic polymers. Tests varying tannin dosage of coagulant and polymer (cationic polymer, nonionic polymer and anionic polymer) were performed on a batch scale, using flotatest. In all the tests were fixed the values of rapid mix (800/s) and flocculation (90/s) velocity gradients, the rapid mix (20 s) and flocculation (15 min) times, saturation pressure (5 Bar) and recycle rate (17%). During the test in the flotation bench scale unity three values of flotation velocities were evaluated: 12.0 cm/min, 16.0 cm/min and 20.0 cm/min. The tests were divided in two phases: the objective of phase 1 was to examine the response of the flotation system with the use of tannin coagulant in the treatment of Monjolinho WWTP UASB effluent (Phase 1A) and also determine the two most suitable dosages of tannin coagulant for the treatment of wastewater from the Monjolinho WWTP UASB tested for each polymer (phase 1B). Phases 1A and 1B were performed with wastewater collected at 8:00 h and 14:00 h, respectively. The objective of phase 2 was to find the optimum dosage of tannin within a narrower range of values, as well as verification of the optimal type and dosage of synthetic polymer (non-ionic, anionic and cationic) to be associated with the tannin coagulant. In phase 1A, it was found that flotation was effective for apparent color removal even to zero coagulant dosage tannin. As for turbidity, there is a marked effect when increasing the coagulant dose, which increased the removal efficiency of this parameter. After obtaining the results of Phase 1B, were chosen for phase 2 two low coagulant dosages which can promote reduction of turbidity by 85%. Besides the two dosages obtained in phase 1B, in phase 2 were evaluated other three between them. Thus, in phase 2 were studied coagulant doses of 65, 75, 85, 95 and 105 mg/L, each one associated with six doses of each one of the studied polymers. Among the treatments employed, it could be seen that the non-ionic polymer and the cationic polymer were the most efficient for treatment by coagulation associated with tannin in flotation. The set of tannin coagulant dosage and polymer which showed satisfactory removal of parameters was 65 mg/L of Tannin with 2.0 mg/L of cationic polymer, reaching 95.2% removal of turbidity, 83% of color apparent, 49.2% of total phosphorus, COD 80.7% and 87.9% of TSS under the conditions found at the time of testing, for post-treatment of Monjolinho WWTP UASB effluent by flotation.
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
PEL_Eloa.pdf (8.69 Mbytes)
Date de Publication
2011-07-18
 
AVERTISSEMENT: Le matériau se réfère à des documents provenant de cette thèse ou mémoire. Le contenu de ces documents est la responsabilité de l'auteur de la thèse ou mémoire.
  • PELEGRINO, E. C. F., Reali, M.A.P., and Escher, A. E. Use of tannin based coagulant in an UASB reactor effluent for post-treatment by flotation. In The 6th International Conference on Flotation for Water and Waste Water Systems, New York, 2012. Proceedings of The 6th International Conference on Flotation for Water and Waste Water Systems.New York : IWA, 2012.
Tous droits de la thèse/dissertation appartiennent aux auteurs