Dissertação de Mestrado
DOI
https://doi.org/10.11606/D.18.2011.tde-11052011-135603
Documento
Autor
Nome completo
Guilherme Caetano do Nascimento
E-mail
Unidade da USP
Área do Conhecimento
Data de Defesa
Imprenta
São Carlos, 2011
Orientador
Banca examinadora
Marra Junior, Wiclef Dymurgo (Presidente)
Aguiar, Monica Lopes
Coury, Jose Renato
Título em português
Avaliação da qualidade do ar em ambientes internos: biblioteca pública
Palavras-chave em português
Ambientes internos
Bibliotecas públicas
Qualidade do ar
Resumo em português
Ao longo de quinze meses, foram monitorados na Biblioteca Pública Amadeu Amaral, da cidade de São Carlos, SP, os níveis de temperatura, umidade relativa, ruído, intensidade luminosa, contaminação por dióxido de carbono, material particulado total (MPT) e suas frações respiráveis (MP1, MP2,5, MP7 e MP10), avaliação da taxa de ventilação e ocupação, concentração de bioaerossóis e sua identificação. Além disso, foi aplicado um questionário aos ocupantes do local com o intuito de levantar as principais reclamações e queixas relacionadas à qualidade do ar interior. Os resultados mostraram o desconforto térmico do local em todas as salas monitoradas, altos níveis de ruído proveniente do ambiente externo, inadequações relativas à iluminação do local e necessidade de uma atenção especial à taxa de ocupação do prédio. Durante alguns momentos das medições, os níveis de ruído ultrapassaram a barreira dos 80 dB(A), que é um valor bem acima do recomendado em normas, revelando-se um fator de risco para seus usuários e funcionários. Não foram encontrados problemas relacionados à contaminação biológica do local, analisando a concentração de bactérias e fungos. A taxa de ventilação possui valor adequado para o piso 1 e a concentração de gás carbônico se manteve de acordo com os padrões estabelecidos em normas. As respostas dos questionários confirmam os principais resultados encontrados para a Biblioteca, como os altos níveis de ruído, o desconforto térmico do local e as inadequações da iluminação. As recomendações são pautadas na necessidade de realização de ensaios gravimétricos da concentração de material particulado e o desenvolvimento de estudos específicos para a adoção de medidas mitigadores da poluição sonora e, também, da adequação das salas para o conforto térmico dos ocupantes.
Título em inglês
Indoor air quality investigation: public library
Palavras-chave em inglês
Air quality
Indoor air
Public libraries
Resumo em inglês
Over fifteen months, levels of temperature, humidity, noise, light intensity, contamination by carbon dioxide, total suspended particles (TSP) and respirable fractions (PM1, PM2.5, PM7 and PM10) were monitored at the Public Library Amadeu Amaral at São Carlos, SP. Investigation of the ventilation rate and occupancy, concentration of bioaerosols and identification were also performed. In addition, a questionnaire was handed over to the occupants of the site in order to raise the main complaints related to indoor air quality. The results showed the discomfort of the place at all rooms monitored, high levels of noise from the outside environment, inadequacies relating to the site illumination and special attention to the building occupancy. During some measurements, the noise levels exceeded the barrier of 80 dB (A), which is above the recommended standards and proved to be a risk factor for its users and employees. No problems were found related to the site biological contamination, analyzing the concentration of bacteria and fungi. The ventilation rate has adequate value to the first floor and carbon dioxide concentration was maintained in accordance with the standards. The questionnaire responses confirm the main findings to the library, such as high noise levels, thermal discomfort and the illumination problem. The main recommendations are based on the need of gravimetric particulate matter investigation and development of specific studies for the adoption of mitigation measures on noise pollution and also the suitability of the rooms to the thermal comfort of occupants.
 
AVISO - A consulta a este documento fica condicionada na aceitação das seguintes condições de uso:
Este trabalho é somente para uso privado de atividades de pesquisa e ensino. Não é autorizada sua reprodução para quaisquer fins lucrativos. Esta reserva de direitos abrange a todos os dados do documento bem como seu conteúdo. Na utilização ou citação de partes do documento é obrigatório mencionar nome da pessoa autora do trabalho.
Data de Publicação
2011-05-13
 
AVISO: O material descrito abaixo refere-se a trabalhos decorrentes desta tese ou dissertação. O conteúdo desses trabalhos é de inteira responsabilidade do autor da tese ou dissertação.
  • ALMEIDA, C. L., et al. MATERIAL PARTICULADO, MICROBIOTA AÉREA E RESISTÊNCIA ANTIMICROBIANA DE STAPHYLOCOCCUS AUREUS EM CIRURGIA ORTOPÉDICA. Revista SOBECC (São Paulo), 2013, vol. 18, p. 45-56.
  • MARRA JUNIOR, W. D., AGUIAR, M. L., e NASCIMENTO, G. C. Avaliação da Qualidade do Ar em Ambientes Internos: Biblioteca Pública. In XVIII Congresso Brasileiro de Engenharia Química, Foz do Iguaçu, 2010. Anais do Congresso Brasileiro de Engenharia Química., 2010.
  • MARRA JUNIOR, W. D., e NASCIMENTO, G. C. Indoor Air Quality Investigation: Public Library. In Environmental Health 2011, Salvador, Brazil, 2011. http://www.environmentalhealthconference.com/., 2011.
Todos os direitos da tese/dissertação são de seus autores
CeTI-SC/STI
Biblioteca Digital de Teses e Dissertações da USP. Copyright © 2001-2024. Todos os direitos reservados.