Tesis Doctoral
DOI
https://doi.org/10.11606/T.18.2016.tde-25072016-152106
Documento
Autor
Nombre completo
Enio Pedone Bandarra Filho
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2002
Director
Tribunal
Saiz Jabardo, José Maria (Presidente)
Milanez, Luiz Fernando
Silveira Junior, Vivaldo
Tavares, Miriam Rocchi
Yanagihara, Jurandir Itizo
Título en portugués
Um estudo experimental da ebulição convectiva de refrigerantes no interior de tubos lisos e internamente ranhurados
Palabras clave en portugués
Ebulição convectiva
Intensificação
Perda de carga
Refrigerantes
Transferência de calor
Tubos microaletados
Resumen en portugués
A presente pesquisa trata de um estudo experimental da transferência de calor e da perda de carga de fluidos refrigerantes puros e suas misturas em mudança de fase convectiva no interior de tubos lisos e aqueles dotados de ranhuras internas. Para tanto, foi desenvolvido um equipamento experimental cujo componente básico é composto por um tubo horizontal, aquecido por intermédio de uma resistência elétrica do tipo fita, aderida à superfície externa do tubo. As condições de ensaio variaram numa ampla faixa, permitindo cobrir as condições verificadas na maioria das instalações frigoríficas. Os resultados experimentais foram agrupados em duas faixas de velocidades mássicas: elevadas (G > ou = 200 kg/s.m2), onde prepondera o padrão anular de escoamento, e reduzidas (G < 200 kg/s.m2), predominando o padrão estratificado. Os principais parâmetros que afetam o coeficiente de transferência de calor, tais como, velocidade mássica, fluxo de calor, tipo de refrigerante, temperatura de evaporação e diâmetro do tubo foram analisados. O desempenho termo-hidráulico, relativo ao efeito combinado da transferência de calor e da perda de carga dos tubos ranhurados, foi sensivelmente superior quando comparados aos tubos lisos. A análise dos resultados experimentais permitiu a proposição de correlações para a perda da carga, avaliada através do multiplicador bifásico, φL, e para coeficiente de transferência de calor, em tubos lisos e ranhurados. As correlações propostas se mostraram adequadas para aplicações práticas, proporcionando desvios reduzidos em relação aos resultados experimentais. Destacam-se as correlações obtidas para o multiplicador bifásico para tubos microaletados e para o coeficiente de transferência de calor para vazões reduzidas em tubos lisos. Diversos registros fotográficos dos principais padrões de escoamento foram levantados, tendo sido importante na análise e entendimento da mudança de fase.
Título en inglés
An experimental study of convective flow boiling of refrigerants inside smooth and microfin tubes
Palabras clave en inglés
Convective flow boiling
Enhancement
Heat transfer
Microfin tube
Pressure drop
Refrigerants
Resumen en inglés
Present research deals with an experimental study of the heat transfer and pressure drop of pure and mixtures of refrigerants undergoing convective boiling inside horizontal smooth and microfin tubes. An experimental apparatus has been developed and constructed whose main component is a horizontal tube electrically heated. Experimental results have been grouped into two mass velocity ranges: the one corresponding to mass velocities lower than 200 kg/s.m2, where the stratified flow pattern is dominant, and that for mass velocities higher than 200 kg/s.m2, where typically the annular flow pattern can be found. Effects over the heat transfer coefficient of physical parameters such as mass velocity, heat flux, diameter, saturation temperature, and refrigerant have been investigated and analyzed. It has been found out that the thermo-hydraulic performance of microfin tubes is better than that of the smooth ones. Empirical correlations have been proposed for both the two-phase flow multiplier and the heat transfer coefficient for different ranges of operating conditions as well as for smooth and microfin tubes. Results from the proposed correlations can be deemed adequate for practical applications given the limited dispersion obtained with respect to their experimental counterpart. Noteworthy are the results obtained from correlations for both the two phase flow multiplier for microfin tubes and the heat transfer coefficient for the lower range of mass velocities in smooth tubes. Finally, worth mentioning is the photographic essay developed in present research involving the flow patterns that occur under convective boiling of refrigerants in horizontal tubes.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2016-07-25
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI
Biblioteca Digital de Tesis y Disertaciones de la USP. Copyright © 2001-2024. Todos los derechos reservados.