Disertación de Maestría
DOI
https://doi.org/10.11606/D.18.2017.tde-07042017-105336
Documento
Autor
Nombre completo
Richard Garcia Alves de Mello
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Carlos, 2000
Director
Tribunal
Saiz Jabardo, José Maria (Presidente)
Hernandez Neto, Alberto
Oliveira Junior, Silvio de
Título en portugués
Modelo de simulação e análise teórico-experimental de serpentinas resfriadoras e desumidificadoras de ar
Palabras clave en portugués
Coeficiente de transferência de calor
Simulação
Trocadores de calor
Resumen en portugués
Em sistemas frigoríficos de compressão a vapor, o evaporador é o equipamento responsável direto pela retirada de calor de ambientes refrigerados. Por esta razão, este componente é a fonte de investigação do presente estudo, o qual teve por objetivo principal a busca por alternativas para a melhoria de desempenho térmico em sistema frigoríficos. Isto posto, o trabalho foi desenvolvido em três frentes de estudo, as quais encontram-se interligadas entre si: desenvolvimento de programa de simulação de serpentinas resfriadoras; realização de ensaios para determinação das capacidades de trocadores de calor; e revisão bibliográfica circunstanciada do coeficiente de transferência de calor do lado do ar. O programa de simulação desenvolvido, o qual tomou como base o modelo proposto por Rich, mostrou-se ser uma ótima ferramenta de trabalho, tanto no meio acadêmico como no industrial. Como conseqüência da elaboração do programa, fez-se uso de correlações já existentes para determinação dos coeficientes de transferência de calor do lado do refrigerante, Bo Pierre, e do lado do ar, McQuiston, sendo esta última escolhida a partir de um sumário de correlações levantadas quando no estudo dos coeficientes de transferência de calor descritos acima. Para que o programa fosse validado como ferramenta de trabalho, foram realizadas simulações dos ensaios das serpentinas testadas e seus resultados confrontados. Tais resultados apresentam uma adequada concordância,possibilitando validar o programa. Os ensaios foram realizados segundo recomendações da norma ASHRAE 25/1992. Dos dados obtidos nos testes, também foi proposto uma correlação para o fator j-Colburn para superfícies secas; no entanto, tratou-se apenas de especular acerca de seu comportamento com as demais correlações, as quais obtiveram boa concordância.
Título en inglés
Model of simulation and analysis of cooling and air dehumidifuing coils
Palabras clave en inglés
Heat exchangers
Heat transfer coefficient
Simulation
Resumen en inglés
In refrigerating systems of compression to vapour, the evaporator is the direct responsible equipment for remove of heat of cooling environments. In this way, the component is the source of investigation of the present study, which had for main objective the search for alternatives to improvement the performance thermal in refrigeration systems. The research was developed in three studies fronts, that are connected each other: development of program of simulation of cooling coils; tests to find the performance of heat exchange; and revision bibliographical of the coefficient of heat transfer of air. The developed simulation program, based in the Rich's model, it showed to be a good work tool, as in the academic, as in the industrial behaviour. As consequence of the elaboration the program, it was used existents correlations to calculation the coefficients of refrigerant heat transfer, Bo Pierre, and to air, McQuiston, the last one was choose from a correlation's summary. Same simulations were made to validated the program of the tested serpentines and the results were confronted. Such results presented an appropriate agreement that contributed to validate the program. The tests were accomplished according to recommendations of the norm ASHRAE 25/1992. One correlation was proposed for the factor j-Colburn for dry surfaces in base of the testes results; however, the purpose was to speculated its behaviour with the other correlations, which obtained good agreement.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.
Fecha de Publicación
2017-04-07
 
ADVERTENCIA: Aprenda que son los trabajos derivados haciendo clic aquí.
Todos los derechos de la tesis/disertación pertenecen a los autores
CeTI-SC/STI