Mémoire de Maîtrise
DOI
https://doi.org/10.11606/D.18.2005.tde-18042006-224115
Document
Auteur
Nom complet
Kenneth de Borja Jaguaribe Júnior
Adresse Mail
Unité de l'USP
Domain de Connaissance
Date de Soutenance
Editeur
São Carlos, 2005
Directeur
Jury
Debs, Mounir Khalil El (Président)
Giongo, Jose Samuel
Silva, Ney Amorim
Titre en portugais
Ligação pilar-fundação por meio de cálice em estruturas de concreto pré-moldado com profundidade de embutimento reduzida
Mots-clés en portugais
cálice de fundação
chave de cisalhamento
colarinho
concreto pré-moldado
investigação experimental
ligação
profundidade de embutimento
Resumé en portugais
Este trabalho consiste na análise experimental da ligação pilar-fundação por meio de cálice em estruturas de concreto pré-moldado, com profundidade de embutimento reduzida em relação a recomendada pela NBR 9062:(1985). No programa experimental, foram ensaiados dois protótipos sob ação de força com grande excentricidade, variando-se o tipo e condição de interface: um com interface lisa e outro com interface rugosa. Em ambos os modelos, procurou-se eliminar a adesão na interface da ligação para representar a situação mais adequada de projeto. Com os resultados experimentais, foi possível analisar o comportamento da cada modelo no que diz respeito as deformações nas armaduras, os deslocamentos no cálice, a configuração das fissuras ocorridas durante o ensaio e a resistência última alcançada por cada modelo. Foi apresentada também uma análise comparativa entre estes modelos e os analisados em trabalho anterior sobre o mesmo tema, sendo que nestes os cálices possuíam profundidades de embutimento recomendados pela norma brasileira. Aplicou-se também os principais modelos de projeto encontrados na literatura com o objetivo de verificar a eficácia de cada um no que diz respeito a capacidade resistente da ligação, comparando-a aos obtidos experimentalmente. Com base em todas estas análises, pôde-se concluir que com a redução da profundidade de embutimento a capacidade resistente do protótipo também diminuiu e os modelos de projeto que melhor representaram os protótipos com comprimento de embutimento maior, não forneceram bons resultados para os cálices com profundidade reduzida
Titre en anglais
Column-foundation connection through socket of precast concrete structures with reduced depth
Mots-clés en anglais
connection
experimental investigation
pedestal walls
precast concrete
shear keys
socket depth
socket foundation
Resumé en anglais
This research is an experimental analysis of column-foundation connection through socket of precast concrete structures, with the reduced depth of the socket comparing to that recommended by the NBR 9062:(1985). The experimental program included two models submitted to normal load with large eccentricity, changing the type and the condition interface: one model had smooth interface and other had rough interface. At both models, it was tried to eliminate the bond on the interface to represent the more appropriate situation of design. With the experimental results, it was possible to analyze each model behavior concerning reinforcements deformation, the socket displacement, cracks configuration during the tests and the maximum strength reached by each model. A comparative analysis was made of these models with those studied at a previous research, that had a depth of the socket recommended by the brazilian normalization. The main design models found at the technical literature were also applied to verify the efficiency of each one for strength capacity of the connection, comparing the results with those obtained experimentally. Based on all analysis, it was possible to conclude that with the depth reduction of the socket, the strength capacity also reduced and the design models that better represented the sockets with the recommended depth no more represented the reduced one
 
AVERTISSEMENT - Regarde ce document est soumise à votre acceptation des conditions d'utilisation suivantes:
Ce document est uniquement à des fins privées pour la recherche et l'enseignement. Reproduction à des fins commerciales est interdite. Cette droits couvrent l'ensemble des données sur ce document ainsi que son contenu. Toute utilisation ou de copie de ce document, en totalité ou en partie, doit inclure le nom de l'auteur.
Mest_Kenneth.pdf (6.42 Mbytes)