• JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
  • JoomlaWorks Simple Image Rotator
 
  Bookmark and Share
 
 
Tesis Doctoral
DOI
https://doi.org/10.11606/T.106.2018.tde-17102018-102649
Documento
Autor
Nombre completo
Alexandre Rigotti Silva
Dirección Electrónica
Instituto/Escuela/Facultad
Área de Conocimiento
Fecha de Defensa
Publicación
São Paulo, 2018
Director
Tribunal
Piantini, Alexandre (Presidente)
Altafim, Ruy Alberto Corrêa
Costa, Eduardo Coelho Marques da
Kanashiro, Arnaldo Gakiya
Kurokawa, Sérgio
Shigihara, Miltom
Título en portugués
Avaliação do comportamento de isoladores de média tensão frente a sobretensões atmosféricas bipolares
Palabras clave en portugués
isoladores elétricos
linhas de distribuição
modelo do efeito disruptivo
onda bipolar
ondas não normalizadas
sobretensões atmosféricas
Resumen en portugués
As linhas de distribuição de energia estão frequentemente expostas a sobretensões causadas por descargas atmosféricas diretas e indiretas. As formas de onda dessas sobretensões podem diferir bastante do impulso atmosférico normalizado utilizado em ensaios para verificação da adequação dos projetos das isolações dos equipamentos frente a sobretensões atmosféricas (1,2/ 50 µs). Diferentes modelos têm sido propostos para se estimar o desempenho das isolações frente a impulsos não normalizados, sendo o modelo do efeito disruptivo (disruptive effect model) um dos mais utilizados. Este trabalho visa avaliar o comportamento de isoladores de média tensão quando sujeitos a sobretensões atmosféricas bipolares oscilatórias. Simulações realizadas usando o "Extended Rusck Model"(ERM) e resultados de medições demonstram que a ocorrência de sobretensões bipolares oscilatórias em linhas de distribuição não é um fato raro, pois descargas atmosféricas podem, sob certas condições, induzir tensões com tais características. Modificações realizadas no circuito de um gerador de impulsos de alta tensão convencional permitiram a geração de tensões bipolares de três períodos distintos: 2,2 µs, 4,1 µs e 6,0 µs. Este trabalho investiga o comportamento de um típico isolador de porcelana tipo pino de 15 kV sujeito a um impulso bipolar, representativo de uma tensão induzida por um raio. Mostra-se que uma modificação no método proposto por Savadamuthu et al. para estimar a suportabilidade do isolamento de pequenos (alguns milímetros) sistemas de isolamento submetidos a tensões oscilantes bipolares leva a resultados promissores em termos de previsão da ocorrência de descargas no isolador de classe 15 kV.
Título en inglés
Evaluation of the behavior of medium insulators voltage to bidirectionally atmospheric overvoltage
Palabras clave en inglés
bipolar oscillating voltages
disruptive effect model
electrical insulators
lightning overvoltages
non-standard waveshapes
power distribution lines
Resumen en inglés
Power lines are often exposed to surges caused by direct and indirect lightning. The waveforms of these overvoltages may differ significantly from the standard lightning impulse used in tests to verify the adequacy of equipment insulation designs against atmospheric overvoltages (1.2/50 µs). Different models have been proposed to estimate the performance of the insulation against non-normalized impulses, with the disruptive effect model being one of the most used. This work aims at evaluating the behavior of medium voltage insulators when subjected to bidirectionally oscillating voltages. Simulations run using the Extended Rusck Model (ERM) and measurement results show that the occurrence of bipolar oscillating overvoltages are not rare on power distribution lines, as lightning strokes can induce, under certain conditions, voltages with such characteristics. Modifications performed in the circuit of a conventional high voltage pulse generator allowed the generation of bipolar voltages of three distinct periods: 2.2 µs, 4.1 µs and 6.0 µs. This work investigates the behavior of a typical 15 kV pin-type porcelain insulator subjected to bipolar impulses representative of lightning-induced voltages. It is shown that a modification on the method proposed by Savadamuthu et al. to estimate the insulation strength of small (a few mm) insulation systems subjected to bipolar oscillating voltages leads to promising results in terms of predicting the occurrence of flashovers on the 15 kV insulator.
 
ADVERTENCIA - La consulta de este documento queda condicionada a la aceptación de las siguientes condiciones de uso:
Este documento es únicamente para usos privados enmarcados en actividades de investigación y docencia. No se autoriza su reproducción con finalidades de lucro. Esta reserva de derechos afecta tanto los datos del documento como a sus contenidos. En la utilización o cita de partes del documento es obligado indicar el nombre de la persona autora.